3 Digital I/O Specifications

3.2.2 100/200-VAC 16-point Output Module

3-30

3) The following diagram shows an example of terminal connections.

Connect power supplies of the same phase to the Common 1 and Common 2 of the
AC I/O Module.

If power supplies of different phase are connected, overheating or fire may
occur.

If using a 100/200-VAC 16-point Output Module, connect a fuse, which complies with
the load specifications, in series with the load.

A protective fuse built into the following 100/200-VAC 16-point Output Modules
does not protect the output element. If a fuse is not connected, a fire or dam-
age to the devices or output circuits may occur if the load is short-circuited or
the circuit overloaded.

Note: (1) Crimp Terminals

Use M3 terminals for crimping to the terminal block.

(2) Recommended Wires

User wires of 1.3mm

2

(AWG16) to 0.5mm

2

(AWG20) to connect to the terminal

block. Use wires of the size more than 1.3 mm

2

(AWG16) for common lines.

Output 1

Output 2

Output 3

Output 4

Output 5

Output 6

Output 7

Output 8

Common 1-1

Common 1-2

Output 9

Output 10

Output 11

Output 12

Output 13

Output 14

Output 15

Output 16

Common 2-1

Common 2-2

Loads

Fuses

100/200 VAC

Terminals

Loads

Fuses

EXAMPLE