4.1 Analog Input Specifications
4-3
4
* Overrange is detected when +10.24 V < Channel input signal or
Channel input signal < -10.24 V
2) Input Characteristics
The following diagram show the input characteristics. Two modes are available:
±2000 mode and 0-4000 mode. The mode is selected by I/O allocation.
Note: (1) For
±2000 mode, if input register value exceeds the range
from -10.24 V to +10.24 V, the analog input value will be
clamped at -2048 or +2048.
(2) For 0-4000 mode, if input register value exceeds the range
from -10.00 V to +10.24 V, the analog input value will be
clamped at 0 or 4048.
Maximum Heating Value
2.3 W
Hot Swapping
(Removal/insertion under power)
Permitted
Approximate Mass
300g
External Dimensions
40.3
×130×103.9 mm (W×H×D)
Recommended Cable
Shielded twisted-pair wires
1.3 mm
2
(AWG16) to 0.5 mm
2
(AWG20)
Item
Specification
Analog input value
Input register value
±2000 mode
0-4000 mode
≤-10.24 V
-2048
0000
-10.00 V
-2000
0000
-5.00 V
-1000
1000
0.00 V
0000
2000
+5.00 V
+1000
3000
+10.00 V
+2000
4000
≥+10.24 V
+2048
4048
Input register value
Analog input value (V)
0-4000 mode
+2000 mode