3.2 Digital Output Module Specifications

3-53

3

If using a 12/24-VDC 64-point Output Module, connect a fuse, which complies with
the load specifications, in series with the load.

A protective fuse built into the following 12/24-VDC 64-point Output Modules
does not protect the output element. If a fuse is not connected, a fire or dam-
age to the devices or output circuits may occur if the load is short-circuited or
the circuit overloaded.

Note: (1) CN2 pins A9 and B9, pins A10 and B10, pins A19 and B19, and pins A20 and

B20 are internally connected. Connect these pins externally as well. Not con-
necting them can cause malfunction.

(2) External Connection Cable

Two pairs of connectors to connect the external output signal and a 64-point I/O
Module Cable to connect to field devices are provided. For details, refer to 3.3
I/O Module Cables.

Loads

Output 64

Output 62

Output 60

Output 58

Output 56

Output 54

Output 52

Output 50

Output 48

Output 46

Output 44

Output 42

Output 40

Output 38

Output 36

Output 34

12/24 VDC

Loads

Loads

Loads

Fuses

Fuses

Fuses

Fuses

CN2 connector
pin numbers

+ Common 4

- Common 4

+ Common 3

- Common 3

Output 63

Output 61

Output 59

Output 57

Output 55

Output 53

Output 51

Output 49

Output 47

Output 45

Output 43

Output 41

Output 39

Output 37

Output 35

+ Common 4

- Common 4

+ Common 3

- Common 3

Output 33

CN2 connector
pin numbers

12/24 VDC

CAUTION