6.4 Precautions on Wiring

6-35

6

If the resistance is too small, the amount of heat generation will increase, and a high
wattage will be required. Here, the wattage for a dummy resistor of 10 k

Ω is calcu-

lated.

The wattage of the dummy resistor is as follows:

Normally, about three times the computed value is used to allow surplus wattage. A
3-W resistor would terefore be used.

6.4.2

AC Output Modules

1) Power Supply Phasing for Output Signals

Connect power supplies of the same phases to the common 1 and common 2 of the
AC I/O Module.

If power supplies of different phases are connected, overheating or fire may
occur.

Fig. 6.13 Power Supply Phasing for Output Signals

W =                                              =                   = 1 W

(Power supply voltage)

R

2

(100 V

10 k

2

CAUTION

Connect power
supply with the
same phase.

Output 1

Output 8

Common 1-1

Common 1-2

Output 9

Output 16

Common 2-1

Common 2-2

Fuses

Loads

Connect power
supply with the
same phase

100 VAC
(200 VAC)