6 Wiring

6.3.6 Interface Circuit

6-16

(b) Open-collector Output Circuit

CN1 connector terminals 30 to 33: Alarm code output are explained below.
Alarm code signals (ALO1, ALO2, ALO3) are output from open-collector transistor output circuits. Con-
nect an open-collector output circuit through a photocoupler, relay circuit, or line receiver circuit.

Note: The maximum allowable voltage and current capacities for open-collector output circuits

are as follows:

• Voltage: 30 VDC
• Current: 20 mA DC

(c) Photocoupler Output Circuit

Photocoupler output circuits are used for servo alarm (ALM), servo ready (/S-RDY), and other sequence out-
put signal circuits. Connect a photocoupler output circuit through a relay circuit or line receiver circuit.

Note: The maximum allowable voltage and current capacities for photocoupler output circuits

are as follows:

• Voltage: 30 VDC
• Current: 50 mA DC

Photocoupler Circuit Example

Relay Circuit Example

Line Receiver Circuit Example

0 V

0 V

SERVOPACK

5 to 12 VDC

Photocoupler

0 V

Relay

5 to 24 VDC

SERVOPACK

SERVOPACK

5 to 12 VDC

0 V

0 V

Relay Circuit Example

Line Receiver Circuit Example

0 V

Relay

5 to 24 VDC

SERVOPACK

5 to 12 VDC

SERVOPACK

0 V