9 Adjustments

9.4.4 Using the Mode Switch (P/PI Switching)

9-18

Using the Torque Reference Level to Switch Modes (Factory Setting)

With this setting, the speed loop is switched to P control when the
value of torque reference input exceeds the torque set in parameter
Pn10C. The factory default setting for the torque reference detection
point is 200% of the rated torque (Pn10C = 200).

„ Operating Example

If the mode switch function is not being used and the SERVOPACK is always operated with PI control, the speed of the
motor may overshoot or undershoot due to torque saturation during acceleration or deceleration. The mode switch function
suppresses torque saturation and eliminates the overshooting or undershooting of the motor speed.

Using the Speed Reference Level to Switch Modes

With this setting, the speed loop is switched to P control when the value
of speed reference input exceeds the speed set in parameter Pn10D.

„ Operating Example

In this example, the mode switch is used to reduce the settling time. It is necessary to increase the speed loop gain to reduce
the settling time. Using the mode switch suppresses overshooting and undershooting when speed loop gain is increased.

Motor speed

Reference speed

Speed

Torque reference

+Pn10C

Torque

reference 0

- Pn10C

PI control

PI control

PI

P

P

Overshoot

Without Mode Switching

With Mode Switching

Undershoot

Motor

speed

Time

Motor

speed

Time

Speed reference

Speed

Pn10D

Motor

speed

Time

P control

PI

PI control

Motor speed

Speed

reference

Long settling time

Increase speed loop gain.

Settling time

Motor

speed

Overshoot

Undershoot

Motor

speed

Time

Motor

speed

Without Mode Switching

With Mode Switching