ix

„ Wiring

• Do not connect a three-phase power supply to the U, V, or W output terminals.

Failure to observe this caution may result in injury or fire.

• Securely connect the power supply terminals and motor output terminals.

Failure to observe this caution may result in fire.

• Do not bundle or run power and signal lines together in the same duct. Keep power and signal lines

separated by at least 30 cm (11.81 in).
Failure to observe this caution may result in malfunction.

• Use twisted-pair shielded wires or multi-core twisted pair shielded wires for signal and encoder (PG)

feedback lines.
The maximum length is 3 m (118.11 in) for reference input lines and is 20 m (787.40 in) for PG feedback lines.

• Do not touch the power terminals for five minutes after turning power OFF because high voltage may still

remain in the SERVOPACK.
Make sure the charge indicator is turned OFF first before starting an inspection.

• Avoid frequently turning power ON and OFF. Do not turn power ON or OFF more than once per minute.

A high charging current flows for 0.2 seconds in the SERVOPACK when power is turned ON. Frequently turning
power ON and OFF causes main power devices such as capacitors and fuses to deteriorate, resulting in unexpected
problems.

• Observe the following precautions when wiring main circuit terminal blocks.

• Remove the terminal block from the SERVOPACK prior to wiring.
• Insert only one wire per terminal on the terminal block.
• Make sure that the core wire is not electrically shorted to adjacent core wires.

• Install the battery at either the host controller or the SERVOPACK of the encoder.

It is dangerous to install batteries at both simultaneously, because that sets up a loop circuit between the batteries.

• Be sure to wire correctly and securely.

Failure to observe this caution may result in motor overrun, injury, or malfunction.

• Always use the specified power supply voltage.

An incorrect voltage may result in damage to the SERVOPACK and burning.

• Take appropriate measures to ensure that the input power supply is supplied within the specified voltage

fluctuation range. Be particularly careful in places where the power supply is unstable.
An incorrect power supply may result in damage to the product.

• Install external breakers or other safety devices against short-circuiting in external wiring.

Failure to observe this caution may result in fire.

• Take appropriate and sufficient countermeasures for each when installing systems in the following

locations.

• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields and magnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies including power supply lines.

Failure to observe this caution may result in damage to the product.

• Do not reverse the polarity of the battery when connecting it.

Failure to observe this caution may damage the battery or cause it to explode.

CAUTION