8 Operation

8.3.6 Instantaneous Power Loss Settings

8-26

8.3.6 Instantaneous Power Loss Settings

Determines whether to continue operation or turn the servo OFF when the power supply voltage to the
SERVOPACK main circuit is instantaneously interrupted.

Pn509

Instantaneous Power Cut Hold Time

Setting Range

Setting Unit

Factory Setting

Setting Validation

20 to 1000

ms

20

Immediately

In power loss detection, the status of the main circuit power supply is detected and OFF status is ignored so servomotor
operation will continue if the servomotor turns back ON within the time set in parameter Pn509.

In the following instances, however, the parameter setting
will be invalid.

• If an insufficient voltage alarm (A.41) occurs during a

power loss with a large servomotor load.

• When control is lost (equivalent to normal power OFF

operation) with loss of the control power supply.

„ IMPORTANT

The maximum setting for the hold time during a power
loss is 1,000 ms, but the hold time for the SERVOPACK
control power supply is about 100 ms. The hold time for
the main circuit power supply depends on the SERVO-
PACK output.
To continue SERVOPACK operation for a power loss that is longer than this, provide an uninterruptible power supply.

Speed

Position

Torque

Power
supply
voltage

Instantaneous power interruption

OFF time t

Servo ON

Servo ON

Servo OFF

Pn509 > t

Pn509 < t

Operation
continued