7 Digital Operator

7.2.6 Automatic Offset-adjustment of Motor Current Detection Signal (Fn00E)

7-12

7.2.6 Automatic Offset-adjustment of Motor Current Detection Signal (Fn00E)

Automatic motor current detection offset adjustment has performed at Yaskawa before shipping. Basically, the
user need not perform this adjustment.
Perform this adjustment only if highly accurate adjustment is required for reducing torque ripple caused by cur-
rent offset. Automatic adjustment is possible only with power supplied to the main circuit power supply and with
the servo OFF.

Execute the automatic offset adjustment if the torque ripple is too big when compared with that of other
SERVOPACKs.

Step

Display after

Operation

Key

Description

1

Press the DSPL/SET Key to select the utility function mode.

2

Press the UP or DOWN Key to select Fn00E.

Note: The enabled digit blinks.

3

Press the DATA/ENTER Key, and the display will be as
shown on the left.

4

Press the DSPL/SET Key.
The offset will be automatically adjusted.
When the adjustment completes, the display shown on the left
blinks for about one second.

5

After about one

second

The display changes from “donE” to the display shown on the
left.

6

Press the DATA/ENTER Key to return to the utility function
mode display Fn00E.

IMPORTANT

DSPL

SET

(DSPL/SET Key)

DATA

ENTER

(DATA/ENTER

Key)

DSPL

SET

(DSPL/SET Key)

DATA

ENTER

(DATA/ENTER

Key)