8 Operation

8.9.1 Internal Torque Limit (Limiting Maximum Output Torque)

8-68

8.9 Limiting Torque

The SERVOPACK provides the following four methods for limiting output torque to protect the machine.

8.9.1 Internal Torque Limit (Limiting Maximum Output Torque)

Maximum torque is always limited to the values set in the following parameters.

Setting

Level

Limiting Method

Applicable

SERVOPACK SGDJ-

Reference

Section

†††

S

†††

P

1

Internal torque limit

Applicable Applicable

8.9.1

2

External torque limit

Applicable Applicable

8.9.2

3

Torque limiting by analog voltage reference

Applicable

N/A

8.9.3

4

External torque limit + Torque limiting by analog voltage reference

Applicable

N/A

8.9.4

Pn402

Forward Torque Limit

Setting Range

Setting Unit

Factory Setting

Setting Validation

0 to 800

%

800

Immediately

Pn403

Reverse Torque Limit

Setting Range

Setting Unit

Factory Setting

Setting Validation

0 to 800

%

800

Immediately

The settings in these parameters are constantly enabled. The setting unit is a percentage of rated torque.
If the torque limit is set higher than the maximum torque of the servomotor, the maximum torque of the servomotor is used
(as is the case with the 800% factory setting).

No Internal Torque Limit

(Maximum Torque Can Be Output)

Internal Torque Limit

Too small a torque limit setting will result in insufficient torque during acceleration and deceleration.

Speed

Position

Torque

Speed

Position

Torque

Speed

Maximum torque

t

Speed

Limiting torque

Pn403

Pn402