Simplified setup using the quick setting group, Quick setting parameters, 3 the drive and programming modes – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 101

Advertising
background image

u

Simplified Setup Using the Quick Setting Group

The Quick Setting Group lists only the basic parameters necessary to set up the Z1000 Bypass. This group expedites the startup

process by showing only the most important bypass parameters.

n

Quick Setting Parameters

Table 4.5

lists the parameters in the Quick Setting Group.

Use the Programming Mode to access parameters not displayed in the Quick Setting Group.

Table 4.5 Quick Setting Group Parameters

No.

Name

Description

Values

Page

A1-06

(127)

Application Preset

Application Sel

0: Standard

0: General

1: Fan

1: Fan General

2: Fan with PI Control

2: Fan PI

3: Return Fan with PI Control

3: Fan ReturnAir/PI

4: Cooling Tower Fan

4: Cooling Tower

5: Cooling Tower Fan with PI Control

5: CoolingTower/PI

6: Pump (Secondary)

6: Pump Secondary

7: Pump with PI Control

7: Pump PI

Default: 0

Range: 0 to 7

118

E1-01

(300)

Input Voltage Setting

Input Voltage

This parameter must be set to the power supply voltage.

WARNING! Electrical Shock Hazard. Drive input voltage (not motor

voltage) must be set in E1-01 for the protective features of the drive to

function properly. Failure to do so may result in equipment damage

and/or death or personal injury.

Default: 230 V

<1>

Min.: 190

<1>

Max.: 240

<1>

145

E1-05

(304)

Maximum Voltage

Max Voltage

Only applicable when E1-03 is set to F.

Default:

<2>

Min.: 0.0 V
Max.: 255.0 V

<1>

148

E2-01

(030E)

Motor Rated Current

Motor Rated FLA

Sets the motor nameplate full load current in amps. Automatically set during

Auto-Tuning.

Default:

<2>

Min.: 10% of drive

rated current

Max.: 200% of
drive rated current

<3>

149

Z1-07

(85CC)

Speed Reference Select

Spd Ref Sel

Determines the source of the Frequency Reference sent from the Bypass

Controller to the Drive.

0: Operator

1: Analog Input

2: Bypass Serial

3: Option Board (CN5)

Default: 1

<4>

Range: 0 to 3

196

Z1-08

(85CD)

Run Command Select

Run Cmd Sel

Determines the source of the Auto Mode Run command used by the Bypass

Controller.

0: Operator

1: Bypass Controller Digital Input

2: Bypass Serial

3: Option Board (CN5)

Default: 1

Range: 0 to 3

197

Z1-09

(85CE)

HAND Mode Drive Speed

Reference

Hand Fref

This is the speed reference used when the Drive is running in HAND mode.

Units are in Hz.

Default: 10.0 Hz

<1>

Min.: 0.0

Max.: 60.0

197

Z1-37

(85EA)

Set Time

Set Time

Changes the LCD display to time setting to set the Real Time Clock.

0: Normal display

1: Displays time and date setting modes
2: Reset time

<5>

Default: 0

Range: 0 to 2

205

Z3-01

(8500)

Serial Communications

Protocol Select

Serial Protocol

Selects the bypass serial communications protocol.

0: Modbus

1: N2

2: P1

3: BACnet

Default: 3

Range: 0, 3

211

Z3-02

(8501)

Serial Communications

Node Address Select

Node Address

Selects the bypass serial communications node address.

Default: 1

Min.: 0

Max.: 127

211

4.3 The Drive and Programming Modes

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

101

4

Start-Up Programming & Operation