Auto-tuning interruption and fault codes, Auto-tuning operation example, Selecting the type of auto-tuning – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 112: 7 auto-tuning, Stationary auto-tuning for line-to-line resistance

Advertising
background image

Table 4.15 Auto-Tuning Input Data

Motor Type

Auto-Tuning Type

Digital Input

Digital Output

Induction

Motor

Stationary Auto-Tuning for Line-to-Line Resistance

Digital input functions

are disabled.

Maintains the status at the start of Auto-Tuning

Rotational Auto-Tuning for V/f Control

Functions the same as during normal operation

n

Notes on Stationary Auto-Tuning

Stationary Auto-Tuning modes analyze motor characteristics by injecting current into the motor for approximately one minute.

WARNING! Electrical Shock Hazard. When executing stationary Auto-Tuning, voltage is applied to the motor before the motor rotates. Do

not touch the motor until Auto-Tuning is completed. Failure to comply may result in injury or death from electrical shock.

WARNING! Sudden Movement Hazard. If installed, do not release the mechanical brake during Stationary Auto-Tuning. Inadvertent brake

release may cause damage to equipment or injury to personnel. Ensure that the mechanical brake release circuit is not controlled by the

drive multi-function digital outputs.

Stationary Auto-Tuning for Line-to-Line Resistance

• Perform when entering motor data manually while using motor cables longer than 50 m.
• If the motor cables have been replaced with cables more than 50 m long after Auto-Tuning has already been performed, use

Stationary Auto-Tuning for line-to-line resistance.

u

Auto-Tuning Interruption and Fault Codes

If tuning results are abnormal or the OFF key is pressed before completion, Auto-Tuning will be interrupted and a fault code

will appear on the HOA keypad.

B

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

A

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

ALM

ALM

DRV-OFF

X.XX Hz/ X.XXA

Tune Proceeding

<

<<

<<< >>>

>>

>

DRV-OFF

Er-03

STOP key

RESET

A – During Auto-Tuning

B – Auto-Tuning Aborted

Figure 4.13 Auto-Tuning Aborted Display

u

Auto-Tuning Operation Example

The following example demonstrates Rotational Auto-Tuning for V/f.

n

Selecting the Type of Auto-Tuning

Step

Display/Result

1. Turn on the power to the drive. The initial display appears.

DRV-OFF

U1-01= 60.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

Freq Ref (AUTO)

LSEQ

LREF

RLY

DRV/BYP

2. Press

or

until the Auto-Tuning display appears.

DRV-OFF

Auto-Tuning

DATA

HELP

Auto

3. Press

to begin setting parameters.

DRV-OFF

T1-

01

= 2 *2*

Line-to-Line

Tuning Mode Sel

DATA

ESC

4. Press

to display the value for T1-01.

DRV-OFF

T1-01=

2

*2*

Line-to-Line

Tuning Mode Sel

DATA

ESC

“0”

4.7 Auto-Tuning

112

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual