u

E2: Motor 1 Parameters

These parameters contain the motor data needed for motor 1. Enter the motor data into these parameters when Auto-Tuning

cannot be performed.

n

E2-01: Motor Rated Current

Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on

the motor nameplate.

No.

Parameter Name

Setting Range

Default

E2-01

Motor Rated Current

10% to 200% of the drive

rated current

Determined by

o2-04

Note:

The number of decimal places in the parameter value depends on the drive model.

Refer to Defaults by Drive Model on page 351

for

details.

n

E2-03: Motor No-Load Current

Set the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive sets

E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor no-load current

listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to receive a copy of the

motor test report.

No.

Parameter Name

Setting Range

Default

E2-03

Motor No-Load Current

0 to [E2-01]

(unit: 0.01 A)

Determined by

o2-04

Note:

The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive

is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motor

capacity is higher than 11 kW.