8 h: terminal functions – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 155

Advertising
background image

Status

Description

Open

Output frequency or motor speed does not match the frequency reference while the drive is running.

Closed

Output frequency or motor speed is within the range of frequency reference ±L4-02.

Note:

Detection works in forward and reverse.

L4-02

L4-02

Frequency
reference

Speed agree 1

ON

OFF

Output Frequency

or Motor Speed

Figure 5.24 Speed Agree 1 Time Chart

Setting 3: User-Set Speed Agree 1 (f

ref

/f

set

Agree 1)

The output closes when the actual output frequency or motor speed and the frequency reference are within the speed agree

width (L4-02) of the programmed speed agree level (L4-01).

Status

Description

Open

Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.

Closed

Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.

Note:

Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.

Frequency reference

Frequency reference

+

L4-02

Frequency reference – L4-02

L4-01

L4-01

+

L4-02

L4-01 – L4-02

Frequency reference

Frequency reference

+

L4-02

Frequency reference – L4-02

–L4-01

–L4-01

+

L4-02

–L4-01 – L4-02

During

Forward

During Reverse

Output frequency

0 Hz

OFF

OFF

OFF

ON

ON

ON

ON

Output frequency

User Set
Speed Agree 1

Figure 5.25 User Set Speed Agree 1 Time Chart

Setting 4: Frequency Detection 1

The output opens when the output frequency or motor speed rises above the detection level set in L4-01 plus the detection

width set in L4-02. The terminal remains open until the output frequency or motor speed fall below the level set in L4-01.

Status

Description

Open

Output frequency or motor speed exceeded L4-01 + L4-02.

Closed

Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.

Note:

Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.

5.8 H: Terminal Functions

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

155

5

Programming