N2 setup parameters, N2 serial communication, F.3 n2 setup parameters – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 423

Advertising
background image

F.3 N2 Setup Parameters

u

N2 Serial Communication

This section describes parameters necessary to set up N2 communications.

n

Z3-01: Serial Communications Protocol Select

Selects the communications protocol.

No.

Name

Setting Range

Default

Z3-01

Serial Communications Protocol Selection

0 to 3

0

Setting 0: MEMOBUS/Modbus
Setting 1: N2
Setting 2: P1
Setting 3: BACnet

n

Z3-02: Serial Communications Node Address Select

Sets the drive slave address used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

Z3-02

Serial Communications Node Address Select

0 to FFH

1FH

Each slave drive must be assigned a unique slave address for serial communications to work. Slave addresses do not need to

be assigned in sequential order, but no two drives may share the same address.

n

Z3-03: Serial Communications Baud Rate Select

Selects the bypass serial communications speed.

No.

Name

Setting Range

Default

Z3-03

Serial Communications Baud Rate Select

0 to 8

3

Setting 0: 1200 bps
Setting 1: 2400 bps
Setting 2: 4800 bps
Setting 3: 9600 bps
Setting 4: 19200 bps
Setting 5: 38400 bps
Setting 6: 57600 bps
Setting 7: 76800 bps
Setting 8: 115200 bps

n

Z3-04: Serial Communications Parity Select

Sets the parity used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

Z3-04

Serial Communications Parity Select

0 to 2

0

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

n

Z3-05: Serial Communications Fault Select

Selects the action to take when a serial communications fault is detected. A serial communications fault is detected when after

last communicating, no communications occurs within the time set to Z3-06.

F.3 N2 Setup Parameters

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

423

F

Metasys N2 Network Protocol

Advertising