L2-02: Momentary Power Loss Ride-Thru Time

Sets the maximum time allowed to ride through a power loss. If power loss operation exceeds this time, the drive will attempt

to accelerate back to the frequency reference. This parameter is valid if L2-01 = 1.

Note:

The amount of time the drive is capable of recovering after a power loss is determined by the capacity of the drive. Drive capacity determines

the upper limit for L2-02.

No.

Name

Setting Range

Default

L2-02

Momentary Power Loss Ride-Thru Time

0.0 to 25.5 s

Determined by o2-04

n

L2-03: Momentary Power Loss Minimum Baseblock Time

Sets the minimum baseblock time when power is restored following a momentary power loss. This determines the time the

drive waits for the residual voltage in the motor to dissipate. Increase this setting if overcurrent or overvoltage occurs at the

beginning of Speed Search, after a power loss, or during DC Injection Braking.

No.

Name

Setting Range

Default

L2-03

Momentary Power Loss Minimum Baseblock Time

0.1 to 5.0 s

Determined by o2-04

n

L2-05: Undervoltage Detection Level (Uv)

Determines the voltage at which a Uv1 fault is triggered or at which the KEB function is activated. This setting rarely needs

to be changed.

No.

Name

Setting Range

Default

L2-05

Undervoltage Detection Level

150 to 220 Vdc

<1>

Determined by E1-01

and o2-04

<1> Values are specific to 208 Vac. Double the value for 480 Vac.

Note:

1. Install an AC reactor option on the input side of the power supply when setting L2-05 below the default value to prevent damage to

drive circuitry.

2. If using KEB Ride-Thru and L2-05 is set too low, then undervoltage in the DC bus (Uv1) will be triggered before KEB Ride-Thru can

be executed. Take caution not to set this value too low.

u

L3: Stall Prevention

The motor may experience excessive slip because it cannot keep up with the frequency reference when the load is too high or

acceleration and deceleration times are too short. If the motor slips during acceleration, it usually causes an overcurrent fault

(oC), drive overload (oL2), or motor overload (oL1). If the motor slips during deceleration, it can cause excessive regenerative

power to flow back into the DC bus capacitors, and eventually cause the drive to fault out from overvoltage (oV). The Stall

Prevention Function prevents the motor from stalling and while allowing the motor to reach the desired speed without requiring

the user to change the acceleration or deceleration time settings. The Stall Prevention function can be set separately for

acceleration, operating at constant speeds, and deceleration.

n

L3-02: Stall Prevention Level during Acceleration

Sets the output current level at which the Stall Prevention during acceleration is activated.

No.

Name

Setting Range

Default

L3-02

Stall Prevention Level during Acceleration

0 to 150%

<1>

<1>

<1> The upper limit and default value is determined by parameter L8-38, Carrier Frequency Derating Selection.

• Lower L3-02 if stalling occurs when using a motor that is relatively small compared to the drive.
• Also set parameter L3-03 when operating the motor in the constant power range.

5.9 L: Protection Functions

170