Setting 14: Fault Reset

When the drive detects a fault condition, the fault output contact closes, the drive output shuts off, and the motor coasts to

stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat). After removing the Run

command, clear the fault either by pressing the RESET key on the HOA keypad or closing a digital input configured as a Fault

Reset (H1-oo = 14).

Note:

Remove the Run command prior to resetting a fault. Fault Reset commands are ignored while the Run command is present.

Setting 19: PI Disable

Close a digital input to indefinitely disable the PI function. When the input is released, the drive resumes PI operation.

Refer

to PI Block Diagram on page 130

.

Setting 24: External Fault

The External fault command stops the drive when problems occur with external devices.
To use the External fault command, set one of the multi-function digital inputs to 24. The HOA keypad will display EFo

where o is the number of the terminal to which the external fault signal is assigned.
For example, if an external fault signal is input to terminal DI-3, “EF3” will be displayed.
The conditions of setting 24 are:
• Terminal status is normally open
• Detection condition is always detected
• Stopping method is coast to stop.

Setting 60: Motor Pre-Heat 1

A DC current can be circulated through the motor windings to create heat and prevent moisture from condensing on the wire.
Motor Pre-Heating can only be initiated by closing a digital input programmed as a Motor Pre-Heat input (H1-oo = 60). The

level of the DC current used by the Motor Pre-Heat function is determined by b2-09

<1>

.

<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.
A Run input will be given priority over a Motor Pre-Heat input and when the Run command is removed, the motor pre-heating

will resume if the Motor Pre-Heat input is still closed.

Motor Pre-Heat 1

command

FWD Run command

Output frequency

Motor Pre-Heat 1

Motor Pre-Heat 1
braking

Motor Pre-Heat 1

Start Frequency

(b2-01)

OFF

OFF

OFF

OFF

ON

ON

Figure 5.21 Motor Pre-Heat 1 Input Timing Diagram

u

H2: Multi-Function Digital Outputs

Note:

H2-oo parameters are available in bypass controller software versions VST800298 and later.

n

H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection

The bypass has three multi-function output terminals.

Table 5.21

lists the functions available for these terminals using H2-01,

H2-02, and H2-03.

No.

Parameter Name

Setting Range

Default

H2-01

Terminal M1-M2 Function Selection (relay)

0 to 160

0: During Run 1

H2-02

Terminal M3-M4 Function Selection (relay)

0 to 160

1: Zero Speed

H2-03

Terminal M5-M6 Function Selection (relay)

0 to 160

2: Speed Agree 1

5.8 H: Terminal Functions

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

153

5

Programming