Z1-16: energy savings mode, Z1-17: energy savings mode frequency, Z1-18: energy savings mode output current level – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 202: Enables and disables the energy savings mode, 0 hz

Advertising
background image

7. Then the drive catches a spinning motor via Speed Search and follows frequency reference to take control.
Refer to

Figure 5.60

for an example of the sequence that is followed when entering and exiting the Energy Savings Mode.

DRIVE FREQUENCY REFERENCE

DRIVE OUPUT FREQUENCY

DRIVE OUTPUT CONTACTOR

BYPASS CONTACTOR

ENERGY FREQ (Z1-17)

ENERGY FREF DBND (Z1-19)

ENERGY FREF DBND (Z1-19)

ENERGY FREQ (Z1-17)

ENERGY FREQ DBND (Z1-20)

ENERGY FREQ DBND (Z1-20)

Energy Savings Mode

Energy

Savings

Time (Z-122)

(Z1-23)

Min Baseblock

T

ime

(L

2-

03

)

Energy Delay Open

(Z

1-

24

)

Energy Delay Open (Z1-24)

Energy Delay Close

(Z

1-

25

)

Drive Enters Baseblock

Start Sequency to

Exit Energy

Savings Mode

Drive Enters Baseblock

Start Sequence to

Enter Energy
Savings Mode

Drive Exits
Baseblock and
Starts

Speed Search

DRIVE OUTPUT CURRENT

OUTPUT IOUT LVL (Z1-18)

ENERGY IOUT DBND (Z1-21)

ENERGY IOUT DBND (Z1-21)

t1

t2

t3

t4

t5

t6

t7

t8

t10 t11

t12 t13 t14 t15

Min Baseblock

T

ime

(L

2-

03

)

t16

Drive Exits Baseblock

Energy Delay Close

(Z

1-

25

)

t9

Energy Fref Increase

Figure 5.60 Drive Bypass Energy Savings Mode Sequence Example

n

Z1-16: Energy Savings Mode

Enables and disables the Energy Savings Mode.

No.

Name

Setting Range

Default

Z1-16

Energy Savings Mode Enable

0 to 2

0

Setting 0: Disable
Setting 1: Enable (Freq)
Setting 2: Enable (Freq + Output Current)

n

Z1-17: Energy Savings Mode Frequency

Sets the value of the drive frequency reference for use in comparison to enter or exit Energy Savings mode.

No.

Name

Setting Range

Default

Z1-17

Energy Savings Mode Frequency

0.0 to 60.0 Hz

<1>

60.0 Hz

<1>

<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.

n

Z1-18: Energy Savings Mode Output Current Level

Allows system to switch when the output current rises above this level of motor rated current for time specified in Z1-22.

No.

Name

Setting Range

Default

Z1-18

Energy Savings Mode Output Current Level

0.0 to 100.0%

0.0%

n

Z1-19: Energy Savings Mode Frequency Reference Deadband

Sets the tolerance around the drive frequency reference value during comparisons to enter or exit Energy Savings mode

5.15 Z: Bypass Parameters

202

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual