H2: Multi-Function Digital Outputs

Note:

H2-oo parameters are available in bypass controller software versions VST800298 and later.

No.

(Addr.

Hex)

Name

Description

Values

Page

H2-01

(040B)

Terminal M1-M2 function

selection (relay)

M1-M2 Func Sel

Refer to H2 Multi-Function Digital Output Settings on pages

320

to

321

for

descriptions of setting values.

Default: 0

Range: 0 to 160

153

H2-02

(040C)

Terminal M3-M4 function

selection (relay)

M3/M4 Func Sel

Default: 1

Range: 0 to 160

153

H2-03

(040D)

Terminal M5-M6 function

selection (relay)

M5/M6 Func Sel

Default: 2

Range: 0 to 160

153

H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

LCD Display

Description

Page

0

During run

During RUN 1

Closed: A Run command is active or voltage is output.

154

1

Zero speed

Zero Speed

Open: Output frequency is above the minimum output frequency set in E1-09.

Closed: Output frequency is below the minimum output frequency set in E1-09.

154

2

Speed agree 1

Fref/Fout Agree1

Closed: Output frequency equals the speed reference (plus or minus the hysteresis

set to L4-02).

154

3

User-set speed agree 1

Fref/Set Agree 1

Closed: Output frequency and speed reference equal L4-01 (plus or minus the

hysteresis set to L4-02).

155

4

Frequency detection 1

Freq Detect 1

Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis

determined by L4-02.

155

5

Frequency detection 2

Freq Detect 2

Closed: Output frequency is greater than or equal to the value in L4-01 with

hysteresis determined by L4-02.

156

6

Drive ready

Drive Ready

Closed: Power up is complete and the drive is ready to accept a Run command.

156

7

DC bus undervoltage

DC Bus Undervolt

Closed: DC bus voltage is below the Uv trip level set in L2-05.

156

8

During baseblock (N.O.) BaseBlk 1

Closed: Drive has entered the baseblock state (no output voltage).

156

B

Torque detection 1

(N.O.)

Trq Det 1 N.O.

Closed: An overtorque or undertorque situation has been detected.

157

C

Frequency reference loss Loss of Ref

Closed: Analog frequency reference has been lost.

157

E

Fault

Fault

Closed: Fault occurred.

157

F

Not Used (Through

mode)

Not Used

Set this value when using the terminal in the pass-through mode.

157

10

Minor fault

Minor Fault

Closed: An alarm has been triggered, or the IGBTs have reached 90% of their

expected life span.

157

11

Fault reset command

active

Reset Cmd Active

Closed: A command has been entered to clear a fault via the input terminals or

from the serial network.

157

13

Speed agree 2

Fref/Fout Agree2

Closed: When drive output frequency equals the frequency reference ±L4-04.

157

14

User-set speed agree 2

Fref/Set Agree 2

Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.

157

15

Frequency detection 3

Freq Detect 3

Closed: When the drive output frequency is less than or equal to the value in L4-03

±L4-04.

158

16

Frequency detection 4

Freq Detect 4

Closed: When the output frequency is greater than or equal to the value in L4-03

±L4-04.

158

17

Torque detection 1

(N.C.)

Trq Det 1 N.C.

Open: Overtorque or undertorque has been detected.

157

1A

During Reverse

Reverse Dir

Closed: Drive is running in the reverse direction.

157

1B

During baseblock (N.C.) BaseBlk 2

Open: Drive has entered the baseblock state (no output voltage).

159

1E

Restart enabled

Dur Flt Restart

Closed: An automatic restart is performed

159

20

Drive overheat pre-

alarm (oH)

OH Prealarm

Closed: Heatsink temperature exceeds the parameter L8-02 value, or an external

device has triggered an oH2 alarm via multi-function input H1-oo = B.

159

2F

Maintenance period

Maintenance

Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay

may require maintenance.

159

B.8 H Parameters: Multi-Function Terminals

320