L3-25: Load Inertia Ratio

Determines the ratio between the rotor inertia and the load. Set this parameter when using Single Drive KEB 2

(L2-29 = 1

<1>

), Intelligent Stall Prevention during deceleration (L3-04 = 2), or the overvoltage suppression function

(L3-11 = 1).

No.

Name

Setting Range

Default

L3-25

Load Inertia Ratio

0.0 to 1000.0

1.0

When set incorrectly, a fairly large current ripple can result during Single Drive KEB 2 (L2-29 = 1

<1>

). This may cause

overvoltage suppression (L3-11 = 1) or other faults such as ov, Uv1, and oC.
Calculate parameter L3-25 in the formula below:

L3-25 =

Machine Inertia

Motor Inertia

<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.

u

L4: Reference Detection

These parameters set up the Loss of Frequency Reference function.

n

L4-05: Frequency Reference Loss Detection Selection

The drive can detect a loss of analog frequency reference from input A1 or A2. Frequency reference loss is detected when the

frequency reference drops below 10% of the reference or below 5% of the maximum output frequency within 400 ms.

100%

400 ms

Analog

frequency

reference

Loss of

Reference

output

time

10%

ON

OFF

Figure 5.45 Loss of Reference Function

Parameter L4-05 selects the operation when a frequency reference loss is detected.

No.

Name

Setting Range

Default

L4-05

Frequency Reference Loss Detection Selection

0, 1

1

Setting 0: Stop

Drive follows the frequency reference (which is no longer present) and stops the motor.

Setting 1: Continue Operation with Reduced Frequency Reference

The drive will continue operation at the percent of the previous frequency value set to parameter L4-06. When the external

frequency reference value is restored, the operation is continued with the frequency reference.

n

L4-06: Frequency Reference at Reference Loss

Sets the frequency reference level at which the drive runs when L4-05 = 1 and when detecting a reference loss. The value is

set as a percentage of the frequency reference before the loss was detected.

No.

Name

Setting Range

Default

L4-06

Frequency Reference at Reference Loss

0.0 to 100.0%

80.0%

5.9 L: Protection Functions

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual