F.6 Metasys N2 Point Database

This section describes the Metasys N2 point database. This database features 100 logical points: 38 Analog Inputs (AI), 32

Analog Outputs (AO), 19 Binary Inputs (BI) and 11 Binary Outputs (BO). These points configure, control, and monitor the

operation of the drive.

u

Metasys N2 Analog Input (AI) Summary

Table F.5 Metasys N2 Analog Input Summary (Bypass to Metasys N2)

Object ID

Object Name

Units

Bypass Parameter

AI 1

Speed Reference

0.01 Hz

U1-01

AI 2

Output Speed

0.01 Hz

U1-02

AI 3

Output Current

0.1 A

U1-03/UB-01 in Drive/Bypass Mode

AI 4

kWatt Hour Meter

kWh

U4-10

AI 5

Output Power

0.1 kWh

U1-08

AI 6

Drive Temperature

1 °C

U4-08

AI 7

PI Feedback

0.01%

U5-01

AI 8

AC Output Voltage

0.1 Vac

U1-06

AI 9

DC Bus Voltage

1 Vdc

U1-07

AI 10

Fault Code

U2-01/UB-09. Reads UB-09 first and if 0 returns U2-01

AI 11

Elapsed Time - Hours

1 hour

U4-01

AI 12

Elapsed Time - 10K Hours

10K hours

U4-01

AI 13

MWatt Hour meter

MWh

U4-11

AI 14

Drive Rated Current

A

n9-01

AI 15

Communication Error Code

Not supported. Always returns 0

AI 16

PI Deviation

0.01%

U5-02

AI 17

PI Output Capacity

0.01%

U5-03

AI 18

PI Reference

0.01%

U5-04

AI 19

Last Fault Code

U2-02

AI 20

Freq Ref @ Fault

0.01 Hz

U2-03

AI 21

Output Freq @ Fault

0.01 Hz

U2-04

AI 22

Output Current @ Fault

0.1 A

U2-05

AI 23

Out Volt Ref @ Fault

0.1 Vac

U2-07

AI 24

DC Bus Volts @ Fault

1 Vdc

U2-08

AI 25

Output Power @ Fault

0.1 kW

U2-09

AI 26

Input Term Status @ Fault

U2-11

AI 27

Output Term Status @ Fault

U2-12

AI 28

Operation Status @ Fault

U2-13

AI 29

Elapsed Operation Time @ Fault

1 hour

U2-14

AI 30

Most Recent Fault

U3-01

AI 31

2nd Most Recent Fault

U3-02

AI 32

3rd Most Recent Fault

U3-03

AI 33

4th Most Recent Fault

U3-04

AI 34

Elapsed Time @ Current Fault

1 hour

U3-11

AI 35

Elapsed Time @ 2nd Fault

1 hour

U3-12

AI 36

Elapsed Time @ 3rd Fault

1 hour

U3-13

AI 37

Elapsed Time @ 4th Fault

1 hour

U3-14

AI 38

Read Parameter Data

F.6 Metasys N2 Point Database

430