F.1 N2 Specifications and Configuration

The bypasses can be monitored and controlled by a controller on a Metasys N2 network (N2) using RS-485 technology. The

bypass act as slaves on the N2 network.
Up to 255 bypasses can communicate on a single N2 network. If more bypasses or N2 devices are required, another N2 network

is required.
The N2 node address is configurable by a parameter in the bypass. This defines the physical address of the bypass on the N2

network.
Once the addressing is set, a controller can initiate communication to the bypass. The bypass will perform the specified function

and then send a response back to the controller.

Z1000 Z1000 Z1000
Bypass Bypass Bypass

N2

Metasys Field
Controller

Figure F.1 Connecting Multiple Bypasses to a Metasys N2 Network

N2 specifications appear in the following table:

Item

Specifications

Interface

RS-485

Communication Parameters

Communication Speed: 9600 bps

Data Length: 8-bit (fixed)

Parity: None

Stop Bit: 1-bit (fixed)

Protocol

Metasys N2

Max Number of Drives

255 per N2 Network Segment

F.1 N2 Specifications and Configuration

420