B.11 o: Operator-Related Settings

The o parameters set up the digital operator displays.

u

o1: HOA Keypad Display Selection

No.

(Addr.

Hex)

Name

Description

Values

Page

o1-03

(502)

HOA Keypad Operator

Display Selection

Display Unit Sel

Sets the units the drive should use to display the frequency reference and motor

speed monitors.

0: 0.01 Hz

0: 0.01 Hz

1: 0.01%

1: 0.01%

(100% = E1-04)

2: r/min

2: r/min

(calculated using the number of motor poles setting in E2-04,

E4-04, or E5-04)

3: User-selected units

3: User Units

(set by o1-10 and o1-11)

Default: 0

Range: 0 to 3

183

o1-09

(51C)

Frequency Reference

Display Units

Fref Disp Unit

Sets unit display for the frequency reference parameters and frequency related

monitors when o1-03 > 40.

0: “WC

0: “WC

(Inch of water)

1: PSI

1: PSI

(Pounds per square inch)

2: GPM

2: GPM

(Gallons per minute)

3: F

3: °F

(Degrees Fahrenheit)

4: CFM

4: CFM

(Cubic feet per minute)

5: CMH

5: CMH

(Cubic meters per hour)

6: LPH

6: LPH

(Liters per hour)

7: LPS

7: LPS

(Liters per second)

8: Bar

8: Bar

(Bar)

9: Pa

9: Pa

(Pascal)

10: C

10: °C

(Degrees Celsius)

11: Mtr

11: Mtr

(Meters)

12: Ft

12: Ft

(Feet)

13: LPM

13: LPM

(Liters per minute)

14: CMM

14: CMM

(Cubic meters per minute)

16: None

16: No Unit

Default: 16

Range: 0 to 14; 16

183

o1-10

(520)

User-Set Display Units

Maximum Value

UserDisp Scaling

These settings define the display values when o1-03 is set to 3.

o1-10 sets the display value that is equal to the maximum output frequency.

o1-11 sets the position of the decimal position.

0: No decimal point

0: No Dec (XXXXX)

1: One decimal point

1: 1 Dec (XXXX.X)

2: Two decimal points

2: 2 Dec (XXX.XX)

3: Three decimal points

3: 3 Dec (XX.XXX)

Default:

<1>

Range: 1 to 60000

184

o1-11

(521)

User-Set Display Units

Decimal Display

UserDisp Dec Sel

Default:

<1>

Range: 0 to 3

184

<1> Default setting is dependent on parameter o1-03, HOA Keypad Display Selection.

u

o2: HOA Keypad Functions

No.

(Addr.

Hex)

Name

Description

Values

Page

o2-04

(508)

Drive Model Selection

Inverter Model #

Enter the drive model. Setting required only if installing a new control board. Default:

Determined by

drive capacity

184