Z3: Bypass Control Communication

No.

(Addr.

Hex)

Name

Description

Values

Page

Z3-01

(8500)

Serial Communications

Protocol Select

Selects the bypass serial communications protocol.

0: Modbus

1: N2

2: P1

3: BACnet

Default: 3

Range: 0 to 3

211

Z3-02

(8501)

Serial Communications

Node Address Select

Selects the bypass serial communications node address.

Default: 1

Min.: 0

Max.: 127

211

Z3-03

(8502)

Serial Communications

Baud Rate Select

Selects the bypass serial communications speed.

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Default: 3

Range: 0 to 8

211

Z3-04

(8503)

Serial Communications

Parity Select

Selects the bypass serial communications parity.

0: No Parity

1: Even Parity

2: Odd Parity

Default: 0

Range: 0 to 2

211

Z3-05

(8504)

Serial Communications

Fault Select

Selects the action to take when a serial communications fault is detected.

0: Ignore. A serial communications loss will result in no action being taken.

1: Alarm only.

2: Fault with EF0. An EF0 will be sent to the drive. If running in Bypass mode,

the bypass contactor will NOT open and the motor will keep running.

3: Fault with EF0 and Open Contactors. An EF0 fault will be sent to the drive

and the bypass contactor (K3) will be opened.

4: Alarm and run at preset speed set in Z3-10. Display AL14 alarm on

Operator.

Default: 1

Range: 0 to 4

211

Z3-06

(8505)

Serial Communications

Fault Time Select

Sets the time allowed to elapse since receiving serial communications before

triggering a communications fault.

A setting of 0.0 will never time out.

Default: 2.0 s

Min.: 0.0

Max.: 99.9

212

Z3-07

(8506)

Serial Communications

Receive to Transmit Wait

Time

Sets the time to delay a serial communications response to a serial

communications command.

Default: 5 ms

Min.: 0

Max.: 99 ms

212

Z3-08

(8507)

BACnet Device Object

Identifier 0

BACnet only.

Sets the least significant word of 22-bit virtual address.

Default: 1

Min.: 0

Max.: FFFF

212

Z3-09

(8508)

BACnet Device Object

Identifier 1

BACnet only.

Sets the most significant word of 22-bit virtual address.

Default: 0

Min.: 0

Max.: 003F

212

Z3-10

(8509)

Cable Loss Preset Frequency When a serial communications fault is detected and Z3-05=4, the resulting

value will become the frequency reference.

Default: 0

Min.: 0.0 Hz

Max.: 60.0 Hz

212

Z3-11

(850A)

Communication Fault

Detection Selection

Communication Fault Detection Selection

0: Disabled. Serial communications fault detection is completely disabled.

1: Enabled. Behavior defined by Z3-05.

Default: 1

Range: 0, 1

212

Z3-12

(850B)

<1>

Network Digital Input Select

Enables and disables control of the digital inputs over a network. Wiring to

the physical digital input is not required.

0: Disable

1: Enable

Default: 0

Range: 0, 1

213

<1> Available in bypass controller software versions VST800298 and later.

B.14 Z: Bypass Parameters

348

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual