Communication Error timeout time not set

properly.

Verify the setting of the serial communications fault time (Z3-06) is set properly.

Controller is not sending data soon enough to stop

the timeout.

Verify the scan rate in the controller that is communicating with the bypass controller is proper. Adjust

as necessary.

HOA Keypad Display

Fault Name

FB15

<1>

Input Phase Loss

Cause

Possible Solutions

Bypass Mode current unbalance condition

exceeded the unbalance level limit set by Z1-50 for

the amount of time specified in Z1-51.

• Check input wiring including fuses, breakers, and connections upstream from the bypass.
• Check the motor wiring and connections.

<1> Available in bypass controller software versions VST800298 and later.

HOA Keypad Display

Fault Name

FB16

<1>

Input Phase Rotation

Cause

Possible Solution

Incorrect phase rotation while Z1-52 is set to 2 in

Bypass Mode.

Check the sequence (phase rotation) of the input wiring to the bypass package.

<1> Available in bypass controller software versions VST800298 and later.

HOA Keypad Display

Fault Name

Fn1

External Fan Fault
External fan failure

Cause

Possible Solution

External cooling fan has malfunctioned

• Cycle power to the drive.
• Check for fan operation.
• Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative

operation time of the fan maintenance timer with U4-04.

• If the cooling fan has exceeded its expected performance life or is damaged in any other way, follow

the replacement instructions in the

Periodic Inspection & Maintenance

chapter.

HOA Keypad Display

Fault Name

FbH

Excessive PI Feedback
PI feedback input is greater than the level set to b5-36 for longer than the time set to b5-37. Set b5-12

to 2 or 5 to enable fault detection.

Cause

Possible Solution

Parameters are set inappropriately

Check b5-36 and b5-37 settings.

Incorrect PI feedback wiring

Correct the wiring.

There is a problem with the feedback sensor

• Check the sensor on the control side.
• Replace the sensor if damaged.

HOA Keypad Display

Fault Name

FbL

PI Feedback Loss
This fault occurs when PI feedback loss detection is programmed to trigger a fault (b5-12 = 2) and

the PI feedback level is below the detection level set to b5-13 for longer than the time set to b5-14.

Cause

Possible Solution

Parameters are set inappropriately

Check b5-13 and b5-14 settings.

Incorrect PI feedback wiring

Correct the wiring.

There is a problem with the feedback sensor

• Check the sensor on the control side.
• Replace the sensor if damaged.

HOA Keypad Display

Fault Name

GF

Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection in models Z1B1D074 to D273 and B052 to B302.

Cause

Possible Solution

6.4 Fault Detection

230