Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 347

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

Page

Z2-09

(856B)

Digital Input 1 Invert Select

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

209

Z2-10

(856C)

Digital Input 2 Invert Select

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

209

Z2-11

(856D)

Digital Input 3 Invert Select

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

209

Z2-12

(856E)

Digital Input 4 Invert Select

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

209

Z2-13

(856F)

Digital Input 5 Invert Select

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

209

Z2-14

(8570)

Digital Input 6 Invert Select

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

209

Z2-15

(8571)

Digital Input 7 Invert Select

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

209

Z2-16

(8572)

Digital Input 8 Invert Select

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

209

Z2-23

(8579)

Digital Output 7 Function

Select

Digital Output 1 Function Select

0: Serial Comm Controlled

1: K1 Drive Input Contactor

2: K2 Drive Output Contactor

3: K3 Bypass Contactor

4: K4 Motor 1 Select

5: K5 Motor 2 Select

6: READY (Drive and Bypass)

7: RUN Active (Drive or Bypass)

8: Drive RUN Active

9: Bypass RUN Active

10: HAND Mode Active

11: OFF Mode Active

12: AUTO Mode Active

13: Drive Mode Selected

14: Bypass Mode Selected

15: Drive or Bypass Fault Active

16: Drive Fault Active

17: Bypass Fault Active

18: Auto Transfer Active

19: Serial RUN Command Active

20: Damper Actuator Output

21: ON Always

22: Loss of Load Detected
23: Run Verify

<1>

99: Not Used

Default: 7

Range: 0 to 23; 99

209

Z2-24

(857A)

Digital Output 8 Function

Select

Default: 10

Range: 0 to 23; 99

209

Z2-25

(857B)

Digital Output 9 Function

Select

Default: 12

Range: 0 to 23; 99

209

Z2-26

(857C)

Digital Output 10 Function

Select

Default: 15

Range: 0 to 23; 99

209

Z2-31

(8581)

<1>

Safety Open Message

Selection

Sets the fault message displayed when an FB01 fault is triggered.

0: Safety Open

1: Fire Stat

2: Freeze Stat

3: Smoke Alarm

4: Over Pressure

5: Low Suction

6: Vibration Switch

Default: 0

Range: 0 to 6

210

<1> Available in bypass controller software versions VST800298 and later.

B.14 Z: Bypass Parameters

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

347

B

Parameter List