B.5 d: References

Reference parameters set the various frequency reference values during operation.

u

d1: Frequency Reference

No.

(Addr.

Hex)

Name

Description

Values

Page

d1-01

(280)

Frequency Reference 1

Reference 1

Sets the frequency reference for the drive. Setting units are determined by

parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 240.00

<1>

142

d1-02

(281)

Frequency Reference 2

Reference 2

Sets the frequency reference for the drive. Setting units are determined by

parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 240.00

<1>

142

d1-03

(282)

Frequency Reference 3

Reference 3

Sets the frequency reference for the drive. Setting units are determined by

parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 240.00

<1>

142

d1-04

(283)

Frequency Reference 4

Reference 4

Sets the frequency reference for the drive. Setting units are determined by

parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 240.00

<1>

142

<1> Range upper limit is determined by parameter E1-04, Maximum Output Frequency.

u

d2: Frequency Upper/Lower Limits

No.

(Addr.

Hex.)

Name

Description

Setting

Page

d2-01

(289)

Frequency Reference Upper

Limit

Ref Upper Limit

Sets the frequency reference upper limit as a percentage of the maximum

output frequency.

Default: 100.0%

Min.: 0.0

Max.: 110.0

143

d2-02

(28A)

Frequency Reference Lower

Limit

Ref Lower Limit

Sets the frequency reference lower limit as a percentage of the maximum

output frequency.

Default: 0.0%

Min.: 0.0

Max.: 110.0

143

d2-03

(293)

Master Speed Reference

Lower Limit

Ref1 Lower Limit

Sets the lower limit for frequency references from analog inputs as a

percentage of the maximum output frequency.

Default: 0.0%

Min.: 0.0

Max.: 110.0

143

u

d3: Jump Frequency

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d3-01

(294)

Jump Frequency 1

Jump Freq 1

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

144

d3-02

(295)

Jump Frequency 2

Jump Freq 2

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

144

d3-03

(296)

Jump Frequency 3

Jump Freq 3

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

144

B.5 d: References

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

315