Z3-08, Z3-09: BACnet Device Object Identifier

These parameters set the Instance Identifier of the BACnet Device Object, where Z3-08 is the least significant word and Z3-09

is the most significant word.

No.

Name

Setting Range

Default

Z3-08

BACnet Device Object Identifier 0

0 to FFFFH

1

Z3-09

BACnet Device Object Identifier 1

0 to 003FH

0

Example 1: Set Device Object Instance Identifier of “1234”.
1234 decimal is equal to 4D2H (hexadecimal).
Set Z3-08 to 4D2H and set Z3-09 to 0.
Example 2: Set Device Object Instance Identifier of “123456”.
123456 decimal is equal to 12D687H.
Set Z3-08 to D687H and set Z3-09 to 12H.

C.4 BACnet Setup Parameters