L5: Fault Restart

After a fault has occurred, Fault Restart attempts to automatically restart the motor and continue operation instead of stopping.
The drive can perform a self-diagnostic check and resume the operation after a fault has occurred. If the self-check is successful

and the cause of the fault has disappeared, the drive restarts by first performing Speed Search (

Refer to b3: Speed Search on

page 122

for details).

Note:

1. The wiring sequence should remove the Forward/Reverse command when a fault is triggered and output is shut off.
2. When the Forward/Reverse command is removed, the drive can perform a self-diagnostic check and attempt to restart the fault

automatically.

WARNING! Sudden Movement Hazard. Do not use the fault restart function in lifting applications. Fault restart may cause the machine to

drop the load, which could result in death or serious injury.

The drive can attempt to restart itself following the faults listed below.

Fault

Name

GF

Ground Fault

LF

Output Open Phase

oC

Overcurrent

oH1

Drive Overheat

oL1

Motor Overload

oL2

Drive Overload

oL3

Overtorque 1

oL4

Overtorque 2

Fault

Name

ov

DC Bus Overvoltage

PF

Input Phase Loss

rH

Braking Resistor Fault

rr

Braking Transistor Fault

Uv1

DC Bus Undervoltage

<1>

STo

Pull-Out Detection

<1> When L2-01 is set to 0 through 2 (continue operation during momentary power loss).

Use parameters L5-01 to L5-05 to set up automatic fault restart.
Set H2-01, H2-02, or H2-03 to 1E. to output a signal during fault restart

<1>

.

<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.

n

L5-01: Number of Auto Restart Attempts

Sets the number of times that the drive may attempt to restart itself.
Parameter L5-05 determines the method of incrementing the restart counter. When the counter reaches the number set to L5-01,

the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter

reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.

No.

Name

Setting Range

Default

L5-01

Number of Auto Restart Attempts

0 to 10 Times

0 Times

n

L5-02: Auto Restart Fault Output Operation Selection

Determines if a fault output is triggered (H2-oo = E) when the drive attempts to restart.

No.

Name

Setting Range

Default

L5-02

Auto Restart Fault Output Operation Selection

0, 1

0

5.9 L: Protection Functions

174

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual