Setting 39: Watt Hour Pulse Output

Outputs a pulse to indicate the watt hours.

Setting 3D: During Speed Search

The output terminal closes while Speed Search is being performed.

Setting 4C: During Fast Stop

The output terminal closes when a Fast Stop is being executed. .

Setting 4D: oH Pre-Alarm Time Limit

The output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat

alarm has not disappeared after 10 frequency reduction operation cycles.

Setting 60: Internal Cooling Fan Alarm

The output closes when the drive internal cooling fan has failed.

Setting 100 to 160: Functions 0 to 60 with Inverse Output

These settings have the same function as settings 0 to 60, but with inverse output. Set as 1oo, where the “1” indicates inverse

output and the last two digits specify the setting number of the function.
Examples:
• Set 108 for inverse output of “8: During Baseblock 1 (N.O.)”.
• Set 14D for inverse output of “4D: oH Pre-Alarm Time Limit”.

u

H3: Multi-Function Analog Inputs

The drive is equipped with multi-function analog input terminals: A1 and A2.

Refer to Multi-Function Analog Input Terminal

Settings on page 163

for a listing of the functions that can be set to these terminals.

n

H3-01: Terminal A1 Signal Level Selection

Selects the input signal level for analog input A1. Set jumper S1 on the terminal board accordingly for voltage input or current

input.

No.

Name

Setting Range

Default

H3-01

Terminal A1 Signal Level Selection

0 to 3

0

Setting 0: 0 to 10 V with Zero Limit

The input level is 0 to 10 Vdc with zero limit. The minimum input level is limited to 0%, so that a negative input signal due

to gain and bias settings will be read as 0%.

5.8 H: Terminal Functions