B.15 defaults by drive model – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 353

Advertising
background image

No.

Name

Unit

Default Settings

Bypass Model Z1B1

B124

B156

B180

B240

B302

o2-04

Drive Model Selection

Hex.

A4

A5

A6

A7

A9

b3-04

V/f Gain during Speed Search

%

60

60

60

60

60

b3-06

Output Current 1 during Speed Search

0.7

0.7

0.7

0.7

0.7

b3-08

Current Control Gain during Speed Search (Speed

Estimation Type)

0.80

0.80

0.80

0.80

0.80

b3-11

Speed Search Method Switching Level (Speed Estimation

Type)

5.0

5.0

5.0

5.0

5.0

C6-02

Carrier Frequency Selection

2

2

2

2

2

E2-01

Motor Rated Current

A

124.0

156.0

180.0

240.0

302.0

E2-03

Motor No-Load Current

A

36

40

49

58

81

L2-03

Momentary Power Loss Minimum Baseblock Time

s

1.3

1.5

1.7

1.7

1.9

L2-05

Undervoltage Detection Level (Uv1)

380

380

380

380

380

L8-02

Overheat Alarm Level

°C

102

112

112

112

111

L8-06

Input Phase Detection Level

27.0

23.0

23.0

26.0

25.0

L8-09

Output Ground Fault Detection Selection

1

1

1

1

1

L8-38

Carrier Frequency Reduction

2

2

2

2

2

B.15 Defaults by Drive Model

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

353