B.15 defaults by drive model – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 353

No.
Name
Unit
Default Settings
–
Bypass Model Z1B1
–
B124
B156
B180
B240
B302
o2-04
Drive Model Selection
Hex.
A4
A5
A6
A7
A9
b3-04
V/f Gain during Speed Search
%
60
60
60
60
60
b3-06
Output Current 1 during Speed Search
–
0.7
0.7
0.7
0.7
0.7
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
–
0.80
0.80
0.80
0.80
0.80
b3-11
Speed Search Method Switching Level (Speed Estimation
Type)
–
5.0
5.0
5.0
5.0
5.0
C6-02
Carrier Frequency Selection
–
2
2
2
2
2
E2-01
Motor Rated Current
A
124.0
156.0
180.0
240.0
302.0
E2-03
Motor No-Load Current
A
36
40
49
58
81
L2-03
Momentary Power Loss Minimum Baseblock Time
s
1.3
1.5
1.7
1.7
1.9
L2-05
Undervoltage Detection Level (Uv1)
–
380
380
380
380
380
L8-02
Overheat Alarm Level
°C
102
112
112
112
111
L8-06
Input Phase Detection Level
–
27.0
23.0
23.0
26.0
25.0
L8-09
Output Ground Fault Detection Selection
–
1
1
1
1
1
L8-38
Carrier Frequency Reduction
–
2
2
2
2
2
B.15 Defaults by Drive Model
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
353
B
Parameter List