Bypass digital input terminal settings – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 207

Advertising
background image

No.

Name

Setting Range

Default

Z2-05

Digital Input 5 Function Select

0 to 36

25

Z2-06

Digital Input 6 Function Select

0 to 36

0

Z2-07

Digital Input 7 Function Select

0 to 36

0

Z2-08

Digital Input 8 Function Select

0 to 36

29

n

Bypass Digital Input Terminal Settings

Table 5.28 Bypass Digital Input Terminal Settings

Setting

Function

Page

0

<1>

Unused (Available for Serial Comms)

Note:

Multiple digital input terminals can

be programmed for “Unused

(Available for Serial Comms)”

(Z2-0o = 0). The drive will run only

when all digital inputs programmed

for “0” are active. This feature

applies to settings 0 and 22. Set all

other selections only once in

parameters Z2-01 to Z2-08.

207

3

DRV Multi-Function Input S3 (H1-03 Setting)

207

4

DRV Multi-Function Input S4 (H1-04 Setting)

207

5

DRV Multi-Function Input S5 (H1-05 Setting)

207

6

DRV Multi-Function Input S6 (H1-06 Setting)

207

7

DRV Multi-Function Input S7 (H1-07 Setting)

207

21

Run (AUTO Mode)

207

22

<1>

Run Enable (Safety)

Note:

Multiple digital input terminals can

be programmed for “Run Enable

(Safety)” (Z2-0o = 22) in bypass

controller software versions

VST800298 and later. The drive will

run only when all digital inputs

programmed for “22” are active.

This feature applies to settings 0 and

22. Set all other selections only once

in parameters Z2-01 to Z2-08.

208

Setting

Function

Page

23

Run Interlock (BAS)

208

24

Remote Transfer to Bypass

208

25

Smoke Purge Bypass Run to Destruction

208

26

Smoke Purge Drive Run to Destruction at Smoke

Purge Preset Speed

208

27

Motor OR Select

208

28

Motor AND Select

208

29

Motor 1 Overload Contact

208

30

Motor 2 Overload Contact

208

31

HAND Select

208

32

AUTO Select

208

33

DRIVE/BYPASS Select

208

34

Fault Reset

208

35

External Fault (EF0)

208

36

External Fault (EFB)

208

<1> Can be set to multiple digital input parameters simultaneously in bypass controller software versions VST800298 and later.

Setting 0: Unused (Available for Serial Comms)

Note:

Multiple digital input terminals can be programmed for “Unused (Available for Serial Comms)” (Z2-0o = 0). The drive will run only when

all digital inputs programmed for “0” are active. This feature applies to settings 0 and 22. All other selections should only be set once in

parameters Z2-01 to Z2-08.

Setting 3: DRV Multi-Function Input S3 (H1-03 Setting)

Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151

for available H1-03 multi-function input settings.

Setting 4: DRV Multi-Function Input S4 (H1-04 Setting)

Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151

for available H1-04 multi-function input settings.

Setting 5: DRV Multi-Function Input S5 (H1-05 Setting)

Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151

for available H1-05 multi-function input settings.

Setting 6:DRV Multi-Function Input S6 (H1-06 Setting)

Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151

for available H1-06 multi-function input settings.

Setting 7: DRV Multi-Function Input S7 (H1-07 Setting)

Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151

for available H1-07 multi-function input settings.

Setting 21: Run (AUTO Mode)

Starts and stops the bypass when Z1-08 is set to 1.

5.15 Z: Bypass Parameters

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

207

5

Programming