Installation Orientation and Spacing

Install the Z1000 Bypass upright as illustrated in

Figure 2.1

to maintain proper cooling.

Figure 2.1 Correct Installation Orientation

n

Single Bypass Installation

Figure 2.2

shows the installation distance required to maintain sufficient space for airflow and wiring. Install the heatsink

against a closed surface to avoid diverting cooling air around the heatsink.

B

A

Side Clearance

A

B

C

Top/Bottom Clearance

D

C

D

A – 50 mm (2.0 in.) minimum
B – 30 mm (1.2 in.) minimum

C – 120 mm (4.7 in.) minimum
D – Airflow direction

Figure 2.2 Correct Installation Spacing

2.2 Mechanical Installation