Z3-05: Serial Communications Fault Select

Selects the action to take when a serial communications fault is detected. A serial communications fault is detected when after

last communicating, no communications occurs within the time set to Z3-06.

No.

Name

Setting Range

Default

Z3-05

Serial Communications Fault Select

0 to 4

1

Setting 0: Ignore
Setting 1: Alarm Only
Setting 2: Fault with EF0

An EF0 fault will be sent to the drive.

Setting 3: Fault with EF0 and Open Contactors

An EF0 fault will be sent to the drive and the bypass contactor (K3) will be opened.

Setting 4: Alarm and run at preset speed set in Z3-10

Display AL14 alarm on operator.

n

Z3-06: Serial Communications Fault Time Select

Sets the time allowed to elapse since receiving serial communications before triggering a communications fault.
A value of 0.0 means to never time out.

No.

Name

Setting Range

Default

Z3-06

Serial Communications Fault Time Select

0.0 s to 99.9 s

2.0 s

n

Z3-07: Serial Communications Receive to Transmit Wait Time

Sets the time to delay a serial communications response to a serial communications command.

No.

Name

Setting Range

Default

Z3-07

Serial Communications Receive to Transmit Wait Time

0 to 99 ms

5 ms

D.4 MEMOBUS/Modbus Setup Parameters

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

381

D

MEMOBUS/Modbus Communications