A.4 Drive Derating Data

The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.

u

Carrier Frequency Derating

Derate the drive according to

Figure A.1

to

Figure A.3

as the carrier frequency increases above the factory default setting.

12.5 kHz

5 kHz

100%

60%

0

Figure A.1 Carrier Frequency Derating (Z1B1D002 to D114 and B001 to B096)

8 kHz

5 kHz

100%

80%

10 kHz

0

Figure A.2 Carrier Frequency Derating (Z1B1D143 to D173 and B124 to B180)

4kHz

100%

60%

10kHz

0

Figure A.3 Carrier Frequency Derating (Z1B1B240 and B302)

u

Altitude Derating

The drive standard ratings are valid for installation altitudes up to 1000 m. For installations from 1000 m to 3000 m, the drive

rated output current must be derated for 0.2% per 100 m.