8 h: terminal functions – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 164

Advertising
background image

Setting 3: Auxiliary Reference 2

Sets the auxiliary frequency reference 2 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 142

for details.

Setting 4: Output Voltage Bias

Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available

only when using V/f Control.

Setting 5: Accel/Decel Time Gain

Adjusts the gain level for the acceleration and deceleration times set to parameters C1-01 through C1-08.
The drive acceleration time is calculated by multiplying the gain level to C1-oo as follows:
C1-oo × Accel/decel time gain = Drive accel/decel time

100%

50%

0

5 V

10 V

1V 2V

20%
10%

Acceleration/deceleration gain from 1 to 10 V

(10 V)

Input Voltage (V)

× 10 (%)

=

Figure 5.36 Accel/Decel Time Gain with Analog Input Terminal

Setting 6: DC Injection Braking Current

The current level used for DC Injection Braking is set as a percentage of the drive rated current.

Drive Rated

Current

0

(4)

100%

10 V

(20 mA)

DC Injection Braking Current Level

Figure 5.37 DC Injection Braking Current Using an Analog Input Terminal

Setting 7: Torque Detection Level

Using this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog input.

The analog input replaces the level set to L6-02. An analog input of 100% (10 V or 20 mA) sets a torque detection level equal

to 100% drive rated current/motor rated torque. Adjust the analog input gain if higher detection level settings are required.

Refer to L6: Torque Detection on page 176

for details on torque detection.

Setting 8: Stall Prevention Level

Allows an analog input signal to adjust the Stall Prevention level.

Figure 5.38

shows the setting characteristics. The drive will

use the lower value of the Stall Prevention level set to L3-06 or the level coming from the selected analog input terminal.

Stall Prevention Level during Run

30%

100%

Analog Input Level

30%

100%

0

Figure 5.38 Stall Prevention During Run Using an Analog Input Terminal

5.8 H: Terminal Functions

164

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual