B.8 H Parameters: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.

u

H1: Multi-Function Digital Inputs

No.

(Addr.

Hex)

Name

Description

Values

Page

H1-03

(400)

Multi-Function Digital Input

Terminal S3 Function

Selection

Term S3 Func Sel

Assigns a function to the multi-function digital inputs through Z2-oo = 3.

Refer to

Table B.3

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 24

Min.: 3

Max.: 60

151

H1-04

(401)

Multi-Function Digital Input

Terminal S4 Function

Selection

Term S4 Func Sel

Assigns a function to the multi-function digital inputs through Z2-oo = 4.

Refer to

Table B.3

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 14

Min.: 3

Max.: 60

151

H1-05

(402)

Multi-Function Digital Input

Terminal S5 Function

Selection

Term S5 Func Sel

Assigns a function to the multi-function digital inputs through Z2-oo = 5.

Refer to

Table B.3

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 3

Min.: 3

Max.: 60

151

H1-06

(403)

Multi-Function Digital Input

Terminal S6 Function

Selection

Term S6 Func Sel

Assigns a function to the multi-function digital inputs through Z2-oo = 6.

Refer to

Table B.3

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 4

Min.: 3

Max.: 60

151

H1-07

(404)

Multi-Function Digital Input

Terminal S7 Function

Selection

Term S7 Func Sel

Assigns a function to the multi-function digital inputs through Z2-oo = 7.

Refer to

Table B.3

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 6

Min.: 3

Max.: 60

151

Table B.3 H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

Description

Page

3

Multi-Step Speed Reference 1

Multi-Step Ref 1

When input terminals are set to Multi-Step Speed References 1 through 3, switching

combinations of those terminals will create a multi-step speed sequence using the frequency

references set in d1-01 through d1-08.

151

4

Multi-Step Speed Reference 2

Multi-Step Ref 2

When input terminals are set to Multi-Step Speed References 1 through 3, switching

combinations of those terminals will create a multi-step speed sequence using the frequency

references set in d1-01 through d1-08.

151

6

Jog reference selection

Jog Freq Ref

Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference

sources.

151

C

Analog terminal input selection

Term AI Enable

Open: Function assigned by H3-14 is disabled.

Closed: Function assigned by H3-14 is enabled.

151

F

<1>

Not Used (Through Mode)

Allows serial communications to control the output.

151

10

Up command

Up Command 1

The drive accelerates when the Up command terminal closes, and decelerates when the Down

command closes. When both terminals are closed or both are open, the drive holds the

frequency reference. The Up and Down commands must always be used in conjunction with

one another.

151

11

Down command

Down Command 1

The drive accelerates when the Up command terminal closes, and decelerates when the Down

command closes. When both terminals are closed or both are open, the drive holds the

frequency reference. The Up and Down commands must always be used in conjunction with

one another.

151

13

<2>

Reverse Jog

Reverse Jog

Closed: Runs reverse at the Jog frequency d1-17

152

14

Fault Reset

Closed: Resets faults if the cause is cleared and the Run command is removed.

153

19

PI disable

PI Disable

Open: PI control enabled

Closed: PI control disabled

153

24

External fault

NO/Always Det
Coast to Stop

Normally Open, Always Detected, Coast to Stop

153

60

Motor pre-heat 1

Motor Preheat 1

Closed: Triggers Motor pre-heat 1

153

<1> Available in bypass controller software versions VST800298 and later.
<2> Available in bypass controller software versions VST800297 and earlier.

B.8 H Parameters: Multi-Function Terminals

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

319