B.3 b: application – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 312

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

Page

b5-06

(1AA)

PI Output Limit

PI Limit

Sets the maximum output possible from the entire PI controller as a percentage

of the maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

131

b5-07

(1AB)

PI Offset Adjustment

PI Offset

Applies an offset to the PI controller output. Set as a percentage of the

maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

131

b5-08

(1AC)

PI Primary Delay Time

Constant

PI Delay Time

Sets a low pass filter time constant on the output of the PI controller.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

131

b5-09

(1AD)

PI Output Level Selection

Output Level Sel

0: Normal output

0: Normal Character

(direct acting)

1: Reverse output

1: Rev Character

(reverse acting)

Default: 0

Range: 0, 1

132

b5-10

(1AE)

PI Output Gain Setting

Output Gain

Sets the gain applied to the PI output.

Default: 1.00

Min.: 0.00

Max.: 25.00

132

b5-11

(1AF)

PI Output Reverse Selection

Output Rev Sel

0: Negative PI output triggers zero limit.

0: limit

1: Rotation direction reverses with negative PI output.

1: Reverse

Note:

When using setting 1, make sure reverse operation is permitted

by b1-04.

Default: 0

Range: 0, 1

132

b5-12

(1B0)

PI Feedback Loss Detection

Selection

Fb loss Det Sel

0: No fault. Digital output only.

0: DO Only - Always

1: Fault detection. Alarm output, drive continues operation.

1: Alarm - Always

2: Fault detection. Fault output, drive output is shut off.

2: Fault - Always

3: Digital Output Always

3: DO Only@PI Enbl

4: Feedback Loss Alarm

4: Alarm @ PI Enbl

5: Feedback Loss Fault

5: Fault @ PI Enbl

Default: 0

Range: 0 to 5

133

b5-13

(1B1)

PI Feedback Loss Detection

Level

Fb loss Det Lvl

Sets the PI feedback loss detection level as a percentage of the maximum

output frequency.

Default: 0%

Min.: 0

Max.: 100

133

b5-14

(1B2)

PI Feedback Loss Detection

Time

Fb loss Det Time

Sets a delay time for PI feedback loss.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

134

b5-15

(1B3)

PI Sleep Function Start

Level

PI Sleep Level

Sets the frequency level that triggers the sleep/snooze function.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

135

b5-16

(1B4)

PI Sleep Delay Time

PI Sleep Time

Sets a delay time before the sleep/snooze function is triggered.

Default: 0.0 s

Min.: 0.0

Max.: 25.5

135

b5-17

(1B5)

PI Accel/Decel Time

PI Acc/Dec Time

Sets the acceleration and deceleration time to PI setpoint.

Default: 0.0 s

Min.: 0.0

Max.: 6000.0

135

b5-18

(1DC)

PI Setpoint Selection

PI Setpoint Sel

0: Disabled

0: Disabled

1: Enabled

1: Enabled

Default: 0

Range: 0, 1

135

b5-19

(1DD)

PI Setpoint Value

PI Setpoint

Sets the PI target value when b5-18 = 1. Set as a percentage of the maximum

output frequency.

Default: 0.00%

Min.: 0.00

Max.: 100.00

135

b5-20

(1E2)

PI Setpoint Scaling

PI Disp Scaling

0: 0.01 Hz units

0: 0.01Hz units

1: 0.01% units

1: 0.01% units

(100% = max output frequency)

2: r/min

2: r/min

(number of motor poles must entered)

3: User-set

3: User Units

(set scaling to b5-38 and b5-39)

Default: 1

Range: 0 to 3

135

b5-34

(19F)

PI Output Lower Limit

PI Out Low Lim

Sets the minimum output possible from the PI controller as a percentage of

the maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

136

b5-35

(1A0)

PI Input Limit

PI Input Limit

Limits the PI control input (deviation signal) as a percentage of the maximum

output frequency. Acts as a bipolar limit.

Default: 1000.0%

Min.: 0.0

Max.: 1000.0

136

b5-36

(1A1)

PI Feedback High Detection

Level

Fb High Det Lvl

Sets the PI feedback high detection level as a percentage of the maximum

output frequency.

Default: 100%

Min.: 0

Max.: 100

134

B.3 b: Application

312

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual