Binary output objects, Binary value objects – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 366

Advertising
background image

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BI16

BYP DI-7 STAT

8781H: bit 6

ON

OFF

R

BI17

BYP DI-8 STAT

8781H: bit 7

ON

OFF

R

BI18

BYP DO-1 STAT

8782H: bit 0

ON

OFF

R

BI19

BYP DO-2 STAT

8782H: bit 1

ON

OFF

R

BI20

BYP DO-3 STAT

8782H: bit 2

ON

OFF

R

BI21

BYP DO-4 STAT

8782H: bit 3

ON

OFF

R

BI22

BYP DO-5 STAT

8782H: bit 4

ON

OFF

R

BI23

BYP DO-6 STAT

8782H: bit 5

ON

OFF

R

BI24

BYP DO-7 STAT

8782H: bit 6

ON

OFF

R

BI25

BYP DO-8 STAT

8782H: bit 7

ON

OFF

R

BI26

BYP DO-9 STAT

8783H: bit 0

ON

OFF

R

BI27

BYP DO-10 STAT

8783H: bit 1

ON

OFF

R

u

Binary Output Objects

Table C.8 Binary Output Objects

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BO1

MF Output M1-M2

0009H:bit 0

ON

OFF

C

BO2

MF Output M3-M4

0009H:bit 1

ON

OFF

C

BO3

MF Output M5-M6

0009H:bit 2

ON

OFF

C

BO4

Ref Sel: PI Setpoint

000FH:bit 1

ON

OFF

C

BO5

Ref Sel: Term S5 IN

8480H:bit 8

ON

OFF

C

BO6

Ref Sel: Term S6 IN

8480H:bit 9

ON

OFF

C

BO7

Refl Sel: Term S7 IN

8480H:bit 10

ON

OFF

C

BO8

BYP DO-07 COMMAND

8403H:bit 6

ON

OFF

C

BO9

BYP DO-08 COMMAND

8403H:bit 7

ON

OFF

C

B010

BYP DO-09 COMMAND

8403H:bit 8

ON

OFF

C

B011

BYP DO-10 COMMAND

8403H:bit 9

ON

OFF

C

u

Binary Value Objects

Table C.9 Binary Value Objects

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BV1

Not Used BV1

BV2

Not Used BV2

BV3

Ext Fault Cmd

8480H:bit 2

FAULT

OFF

C

BV4

Fault Reset Cmd

8480H:bit 3

RESET

OFF

C

BV5

Not Used BV5

BV6

Not Used BV6

BV7

MF Input 3 Cmd

8480H:bit 6

ON

OFF

C

BV8

MF Input 4 Cmd

8480H:bit 7

ON

OFF

C

BV9

MF Input 5 Cmd

8480H:bit 8

ON

OFF

C

BV10

MF Input 6 Cmd

8480H:bit 9

ON

OFF

C

BV11

MF Input 7 Cmd

8480H:bit 10

ON

OFF

C

BV12

Set Fault Contact Cmd

0009H:bit 6

ENABLE

OFF

C

BV13

RUN-STOP

0020H:bit 0

RUN

OFF

R

BV14

REV-FWD

0020H:bit 1

REV

FWD

R

BV15

READY

0020H:bit 2

READY

OFF

R

BV16

FAULT

0020H:bit 3

FAULTED

OFF

R

C.6 BACnet Objects Supported