Metasys n2 analog output (ao) summary, Metasys n2 binary input (bi) summary – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 431

Advertising
background image

u

Metasys N2 Analog Output (AO) Summary

Table F.6 Metasys N2 Analog Output Summary (Bypass to Metasys N2)

Object ID

Object Name

Units

Default Value

Bypass Parameter

AO 1

Speed Command

0.01 Hz

AO 2

Acceleration Time

seconds

30.0

C1-01

AO 3

Deceleration Time

seconds

30.0

C1-02

AO 4

PI Proportional Gain

2.00

b5-02

AO 5

PI Integral Time

seconds

5.0

b5-03

AO 6

Stall Prevention Level – Run

%

120

L3-06

AO 7

Stall Prevention Level – Accel

%

120

L3-02

AO 8

Frequency Reference Selection

0

Z1-07

AO 9

Run Command Selection

1

Z1-08

AO 10

PI Mode Select

0

b5-01

AO 11

Frequency Command Upper Limit

% of Max

100.0

d2-01

AO 12

Frequency Command Lower Limit

% of Max

0.0

d2-02

AO 13

Motor Rated Current

A

Motor model dependent

E2-01

AO 14

Jump Frequency 1

0.1 Hz

0.0

d3-01

AO 15

Jump Frequency 2

0.1 Hz

0.0

d3-02

AO 16

Jump Frequency 3

0.1 Hz

0.0

d3-03

AO 17

Jump Frequency Bandwidth

0.1 Hz

1.0

d3-04

AO 18

Number of Auto Restarts

0

L5-01

AO 19

Operator Display Mode

0

o1-03

AO 20

Power Loss Ride-Thru

seconds

Drive model dependent

L2-02

AO 21

Cable Loss Timeout

seconds

2.0

Z3-06

AO 22

Cable Loss Speed

0.01 Hz

0.00

Z3-10

AO 23

PI Integral Limit

0.1%

100.0

b5-04

AO 24

PI Upper Limit Value

0.1

100.0

b5-06

AO 25

PI Offset Adjustment

0.1

0.0

b5-07

AO 26

PI Primary Delay Time

0.01

0.00

b5-08

AO 27

PI Feedback Reference Missing

Detection Select

1

0

b5-12

AO 28

PI Feedback Reference Missing

Detection Level

1%

0

b5-13

AO 29

PI Feedback Reference Missing

Detection Time

0.1 s

1.0

b5-14

AO 30

Read Parameter Number

AO 31

Write Parameter Number

AO 32

Write Parameter Data

u

Metasys N2 Binary Input (BI) Summary

Table F.7 Metasys N2 Binary Input Summary (Bypass to Metasys N2)

Object ID

Object Name

Default

Off (0) State

On (1) State

BI 1

Run/Stop Monitor

0

Stopped

Running

BI 2

Forward/Reverse Monitor

0

Forward

Reverse

BI 3

Drive Ready Monitor

0

Not Ready

Ready

BI 4

Fault Monitor

0

Not Faulted

Faulted

BI 5

Zero Speed

0

Not Zero Speed

Zero Speed

BI 6

Speed Agree

0

Not Speed Agree

Speed Agree

BI 7

Minor Fault

0

No Minor Fault

Minor Fault

BI 8

Major Fault

0

No Major Fault

Major Fault

BI 9

Drive Communication Error Monitor

0

No Error

Error

F.6 Metasys N2 Point Database

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

431

F

Metasys N2 Network Protocol

Advertising