Z1-08: run command select, Z1-09: hand mode drive speed reference – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 197

Advertising
background image

Input terminals A1 and A2 can accept a current input signal. Refer to

Table 5.27

to set terminals A1 and A2 for current input.

Table 5.27 Analog Input Settings for Frequency Reference Using a Current Signal

Terminal

Signal

Level

Parameter Settings

Notes

Signal Level

Selection

Function

Selection

Gain

Bias

A1

4 to 20 mA

H3-01 = 2

H3-02 = 0

(Frequency

Reference Bias)

H3-03

H3-04

Make sure to set Jumper S1 on the

control board to “I” for current

input.

0 to 20 mA

H3-01 = 3

A2

4 to 20 mA

H3-09 = 2

H3-10 = 0

(Frequency Bias)

H3-11

H3-12

0 to 20 mA

H3-09 = 3

Drive

A1 Analog Input 1

0 or 4 to 20 mA

AC Analog input common

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

V

I

A1 A2

Jumper S1
Terminal A1/A2
Voltage/Current
Selection

V

I

A1 A2

Figure 5.55 Setting the Frequency Reference as a Current Signal to Terminal A2

Switching between Main/Auxiliary Frequency References

The frequency reference input can be switched between the analog terminals A1 and A2 using multi-speed inputs.

Setting 2: BACnet, MEMOBUS/Modbus, P1, or N2 Communications

This setting requires entering the frequency reference via the RS-485 serial communications port (control terminals TXRX+

and TXRX-).

Setting 3: Option Card

This setting requires entering the frequency reference via an option board plugged into connector CN5 on the bypass control

board. Consult the option card manual for instructions on integrating the drive with the communication system.

n

Z1-08: Run Command Select

Determines the source of the Auto Mode RUN command used by the Bypass Controller.

No.

Name

Setting Range

Default

Z1-08

Run Command Select

1 to 3

1

Setting 0: HOA Keypad
Setting 1: Bypass Controller Digital Input

This setting requires entering the Run command via the digital input terminals.

Setting 2: BACnet or MEMOBUS/Modbus Communications

This setting requires entering the Run command via serial communications by connecting the RS-485 serial communication

cable to control terminals TXRX+ and TXRX- on the terminal block.

Refer to MEMOBUS/Modbus Configuration on page

376

for instructions.

Setting 3: Option Card

This setting requires entering the Run command via the communication option board by plugging a communication option

board into the CN5 port on the control PCB. Refer to the option card manual for instructions on integrating the bypass into

the communication system.

n

Z1-09: HAND Mode Drive Speed Reference

The speed reference used when the Drive is running in HAND mode.

5.15 Z: Bypass Parameters

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

197

5

Programming

Advertising