L6: Torque Detection

No.

(Addr.

Hex)

Name

Description

Values

Page

L6-01

(4A1)

<1>

Torque Detection Selection

1

0: Disabled

1: oL3 detection only active during speed agree, operation continues after

detection

2: oL3 detection always active during run, operation continues after detection

3: oL3 detection only active during speed agree, output shuts down on an oL3

fault

4: oL3 detection always active during run, output shuts down on an oL3 fault

5: UL3 detection only active during speed agree, operation continues after

detection

6: UL3 detection always active during run, operation continues after detection

7: UL3 detection only active during speed agree, output shuts down on an oL3

fault

8: UL3 detection always active during run, output shuts down on an oL3 fault

Default: 0

Range: 0 to 8

177

L6-02

(4A2)

Torque Detection Level 1

Torq Det 1 Lvl

Sets the overtorque and undertorque detection level.

Default: 15%

Min.: 0

Max.: 300

178

L6-03

(4A3)

Torque Detection Time 1

Torq Det 1 Time

Sets the time an overtorque or undertorque condition must exist to trigger

torque detection 1.

Default: 10.0 s

Min.: 0.0

Max.: 10.0

178

L6-13

(62E)

Motor Underload Protection

Selection

Underload Select

Sets the motor underload protection (ULo) based on motor load.

0: Overtorque/undertorque detection enabled

0: Base Freq Enable

1: Base frequency motor load enabled

1: Max Freq Enable

Default: 0

Range: 0, 1

178

L6-14

(62F)

Motor Underload Protection

Level at Minimum

Frequency

Underload Level

Sets the UL6 detection level at minimum frequency by percentage of drive

rated current.

Default: 15%

Min.: 0

Max.: 300

178

<1> Available in bypass controller software versions VST800298 and later.

u

L8: Drive Protection

No.

(Addr.

Hex)

Name

Description

Values

Page

L8-02

(4AE)

Overheat Alarm Level

OH Pre-Alarm Lvl

An overheat alarm occurs when heatsink temperature exceeds the L8-02 level. Default:

<1>

Min.: 50 °C

Max.: 150 °C

179

L8-05

(4B1)

Input Phase Loss Protection

Selection

Inp Ph Loss Det

Selects the detection of input current phase loss, power supply voltage

imbalance, or main circuit electrolytic capacitor deterioration.

0: Disabled

0: Disabled

1: Enabled

1: Enabled

Default: 1

Range: 0, 1

179

L8-06

(4B2)

Input Phase Detection Level

Inp Ph Loss Lvl

When ripple is observed in the DC bus, expansion of the input bias is

calculated. This value becomes the input phase if the difference between the

maximum and minimum values of the ripple is greater than the value set to

L8-06.

Detection Level = 100% = Voltage class x √2

Default:

<1>

Min.: 0.0%

Max.: 50.0%

179

L8-07

(4B3)

Output Phase Loss

Protection Selection

Outp Ph Loss Det

0: Disabled

0: Disabled

1: Enabled

1: 1PH Loss Det

(triggered by a single phase loss)

2: Enabled

2: 2/3PH Loss Det

(triggered when two phases are lost)

Default: 1

Range: 0 to 2

179

L8-09

(4B5)

Output Ground Fault

Detection Selection

Grnd Flt Det Sel

0: Disabled

0: Disabled

1: Enabled

1: Enabled

Default:

<1>

Range: 0, 1

180

L8-38

(4EF)

Carrier Frequency

Reduction

Fc Reduct dur OL

0: Disabled

0: Disabled

1: Enabled below 6 Hz

1: Active below 6Hz

2: Enabled for the entire speed range

2: Active @ any Spd

Default:

<1>

Range: 0 to 2

180

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.