Programming errors, 6 programming errors – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 246

Advertising
background image

6.6 Programming Errors

u

Programming Error Codes, Causes, and Possible Solutions

A Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an inappropriate

value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does not

trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to

Table 6.10

for the appropriate action. When

an oPE appears on the HOA keypad display, press the ENTER button to view U1-18 and see which parameter is causing the

oPE.

Table 6.10 oPE Codes, Causes, and Possible Solutions

HOA Keypad Display

Error Name

oPE01

Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.

Cause

Possible Solutions

The drive model selection (o2-04) and the actual

capacity of the drive are not the same

Correct the value set to o2-04.

HOA Keypad Display

Error Name

oPE02

Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.

Cause

Possible Solutions

Parameters were set outside the possible setting

range

• Set parameters to the proper values by checking the modified constants menu and verifying that

settings are within the limits.

• Set Z1-01 to 1 to re-initialize the drive and bypass.
Set parameters to the proper values by checking the modified constants menu and verifying that

settings are within the limits.

Note:

When multiple errors occur simultaneously, other errors are given precedence over oPE02

HOA Keypad Display

Error Name

oPE03

Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs Z2-01 to Z2-08.

Cause

Possible Solutions

• The same function is assigned to two

multi-function inputs

• Excludes “Not used” and “External Fault”

• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.

Settings for N.C. and N.O. input for the following

functions were selected simultaneously:
• External Search Command 1 and External

Search Command 2 (61 vs. 62)

• Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
• KEB for Momentary Power Loss and High Slip

Braking

(65, 66, 7A, 7B vs. 68)

• KEB Command 1 and KEB Command 2 (65, 66

vs. 7A, 7B)

• FWD Run Command (or REV) and FWD/REV

Run Command (2-wire) (40, 41 vs. 42, 43)

• Drive Enable (60 vs. 6A)

• Check if contradictory settings have simultaneously been assigned to the multi-function input

terminals.

• Correct setting errors.

6.6 Programming Errors

246

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual