O: operator-related settings, O1: hoa keypad display selection, 11 o: operator-related settings – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 183

Advertising
background image

5.11 o: Operator-Related Settings

These parameters control the various functions, features, and display of the HOA keypad.

u

o1: HOA Keypad Display Selection

These parameters determine the data display on the HOA keypad.

n

o1-03: HOA Keypad Display Selection

Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units before setting

parameters o1-10 and o1-11.

No.

Name

Setting Range

Default

o1-03

HOA Keypad Display Selection

0 to 3

0

Setting 0: 0.01 Hz Units
Setting 1: 0.01% Units (100% = Max Output Frequency)
Setting 2: r/min Units (Calculated by the Max Output Frequency and the Number of Motor Poles)
Setting 3: User-set Units (Use o1-10, o1-11)

Set the value used for the maximum frequency reference to o1-10. Set the placement of the decimal point in this number to

o1-11.
For example, to have the maximum output frequency displayed as “100.00”, set o1-10 = 1000 and o1-11 = 2 (i.e., 1000 with

2 decimal points).

Note:

1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:

U1-01: frequency reference

U1-02: output frequency

U1-16: output frequency after softstarter (accel/decel ramp generator)

d1-01 to d1-17: frequency references

2. Setting o1-03 to 2 requires entering the number of motor poles to E2-04 and E5-04.

n

o1-09: Frequency Reference Display Units

Sets unit display for the frequency reference parameters and frequency related monitors when o1-03 > 40.

No.

Name

Setting Range

Default

o1-09

Frequency Reference Display Units

0 to 16

16

Setting 0: Inch of Water (“WC)
Setting 1: Pounds per Square Inch (PSI)
Setting 2: Gallons per Minute (GPM)
Setting 3: Degrees Fahrenheit (F)
Setting 4: Cubic Feet per Minute (CFM)
Setting 5: Cubic Meters per Hour (CMH)
Setting 6: Liters per Hour (LPH)
Setting 7: Liters per Second (LPS)
Setting 8: Bar (Bar)
Setting 9: Pascals (Pa)
Setting 10: Degrees Celsius (C)
Setting 11: Meters (Mtr)
Setting 12: Ft (Feet)
Setting 13: Liters per Minute (LPM)
Setting 14: Cubic Meters per Minute (CMM) No unit
Setting 15: Custom Units (Determined by o1-12)
Setting 16: None

5.11 o: Operator-Related Settings

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

183

5

Programming

Advertising