VFD RUN COMMAND

VFD OUTPUT FREQUENCY

DAMPER ACTUATOR OUTPUT

BAS INTERLOCK INPUT

2

t

1

t

VFD FREQUENCY REFERENCE

Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 10.0 sec

Z1-15 Interlck Wait Tm

t3

FAULT: FB02 BAS Ilock Open

Figure 5.57 Run Delay with Preset Speed Example: BAS Interlock Wait Time Fault

VFD RUN COMMAND

VFD OUTPUT FREQUENCY

DAMPER ACTUATOR OUTPUT

BAS INTERLOCK INPUT

t1

t2

t3

VFD FREQUENCY REFERENCE

Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 1 (Enable)
Z1-14 Run Delay Fref = 30.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)

Z1-14 Run Delay Fref

t4

Figure 5.58 Run Delay with Preset Speed Example: Preset Speed

5.15 Z: Bypass Parameters

200

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual