6.9 Troubleshooting without Fault Display

This section describes troubleshooting problems that do not trip an alarm or fault.
The following symptoms indicate that the drive is not set correctly for proper performance with the motor.

Refer to Motor

Performance Fine-Tuning on page 220

for guidance on troubleshooting.

• Motor hunting and oscillation
• Poor motor torque
• Poor speed precision
• Poor motor torque and speed response
• Motor noise

u

Common Problems

Common Problems

Page

Cannot Change Parameter Settings

253

Motor Does Not Rotate Properly after Pressing the AUTO

Button or after Entering External Run Command

Motor Does Not Rotate

254

Motor Rotates in the Opposite Direction from the Run

Command

255

Motor Rotates in One Direction Only

255

Motor is Too Hot

255

oPE02 Error Occurs When Lowering the Motor Rated Current Setting

256

Motor Stalls During Acceleration or With Large Loads

256

Drive Frequency Reference Differs from the Controller Frequency Reference Command

256

Excessive Motor Oscillation and Erratic Rotation

257

Deceleration Takes Longer Than Expected

257

Noise From Drive or Motor Cables When the Drive is Powered On

257

Ground Fault Circuit Interrupter (GFCI) Trips During Run

257

Connected Machinery Vibrates When Motor Rotates

Unexpected Noise from Connected Machinery

257

Oscillation or Hunting

258

PI Output Fault

258

Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)

258

Output Frequency is not as High as Frequency Reference

258

Sound from Motor

258

Motor Does Not Restart after Power Loss

259

u

Cannot Change Parameter Settings

Cause

Possible Solutions

The drive is running the motor

(i.e., the Run command is present).

• Stop the drive and switch over to the Programming Mode.
• Most parameters cannot be edited during run.

The operator is not in the Parameter Setup Mode

(the screen will display “PAr”).

• See what mode the operator is currently set for.
• Parameters cannot be edited when in the Setup Mode (“STUP”). Switch modes so that “PAr”

appears on the screen.

Refer to The Drive and Programming Modes on page 99

.

A multi-function contact input terminal is set to allow

or restrict parameter editing

(H1-01 through H1-07 = 1B).

• When the terminal is open, parameters cannot be edited.
• Turn on the multi-function contact input set to 1B.

The wrong password was entered.

• If the password entered to A1-04 does not match the password saved to A1-05, then drive

settings cannot be changed.

• Reset the password.
If you cannot remember the password:

Scroll to Z1-02. Press

OFF

and

simultaneously. Parameter Z1-03 will appear.

• Set a new password to parameter Z1-03.

6.9 Troubleshooting without Fault Display