Power ratings, Three-phase 208 vac models z1b1d002 to d046, A.1 power ratings – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 296

Advertising
background image

A.1 Power Ratings

u

Three-Phase 208 Vac Models Z1B1D002 to D046

Table A.1 Power Ratings (Three-Phase 208 V)

Item

Specification

Bypass Model Z1B1

D002

D003

D004

D007

D010

D016

D024

D030

D046

Maximum

Applicable

Motor

Capacity

<1>

HP

0.5

0.75

1

2

3

5

7.5

10

15

kW

0.37

0.55

0.74

1.5

2.2

3.7

5.5

7.5

11

Input

Input Current (A)

<2>

2.9

4.0

5.1

8.0

11.1

17.2

24.7

31.3

46.7

Rated Voltage

Rated Frequency

Three-phase 208 Vac 50/60 Hz

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Output

Rated Output Current (A)

2.4

<3>

3.5

<3>

4.6

<3>

7.5

<3>

10.6

<3>

16.7

<3>

24.2

<3>

30.8

<3>

46.2

<3>

Overload Tolerance

110% of rated output current for 60 s

150% peak

Carrier Frequency

User adjustable between 1 and 12.5 kHz

(Maximum Frequency varies with Rated Output Capacity)

Maximum Output Voltage (V)

Three-phase 208 Vac

Maximum Output Frequency (Hz)

240 Hz

Harmonics

Reduction

DC Link Choke

Built-in

EMC

Filter (IEC/EN 61800-3 Category 2)

Built-in

<1> The motor capacity (HP) refers to an NEC Table 430.250 208 V motor. The rated output current of the drive output amps should be equal to or

greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> Carrier frequency is set to 5 kHz. Current derating is required to raise the carrier frequency.

A.1 Power Ratings