Setting 0: “WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPM (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)

n

b5-47: Reverse Operation Selection 2 by PI Output

Determines whether a negative PI output reverses the direction of drive operation. When the PI function is used to trim the

frequency reference (b5-01 = 3), this parameter has no effect and the PI output will not be limited

(same as b5-11 = 1).

No.

Name

Setting Range

Default

b5-47

Reverse Operation Selection 2 by PI Output

0, 1

1

Setting 0: 0 Limit (Reverse Disabled)

Negative PI output will be limited to zero and the drive output will be stopped.

Setting 1: Reverse Enabled

Negative PI output will cause the drive to run in the opposite direction.

n

Fine-Tuning PI

Follow the directions below to fine tune PI control parameters:

Table 5.5 PI Fine Tuning

Goal

Tuning Procedure

Result

Suppress overshoot

Increase the integral time (b5-03)

Response

Before adjustment

After adjustment

Time

Achieve stability quickly while

allowing some overshoot

Decrease the integral time (b5-03)

Response

Before adjustment

After adjustment

Time

5.2 b: Application

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

137

5

Programming