C: tuning, C1: acceleration and deceleration times, 4 c: tuning – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 139: C2: s-curve characteristics

Advertising
background image

5.4 C: Tuning

C parameters set the characteristics for acceleration, deceleration, and S-curves. Other parameters in the C group cover settings

for slip compensation, torque compensation, and carrier frequency.

u

C1: Acceleration and Deceleration Times

n

C1-01 and C1-02: Accel, Decel Time 1

Four different sets of acceleration and deceleration times can be set in the drive by digital inputs, motor selection, or switched

automatically.
Acceleration time parameters always set the time to accelerate from 0 Hz to the maximum output frequency (E1-04).

Deceleration time parameters always set the time to decelerate from maximum output frequency to 0 Hz. C1-01 and C1-02

are the default active accel/decel settings.

No.

Parameter Name

Setting Range

Default

C1-01

Acceleration Time 1

0.1 to 6000.0 s

30.0 s

C1-02

Deceleration Time 1

n

C1-09: Fast Stop Time

Sets a special deceleration used when a select group of faults occur or when closing a digital input configured as H1-oo =

15 (N.O. input) or 17 (N.C. input). A momentary closure of the digital input will trigger the Fast Stop operation; it does not

have to be closed continuously.
The drive cannot be restarted after initiating a Fast Stop operation until after completing deceleration, clearing the Fast Stop

input, and cycling the Run command.
A digital output programmed for “During Fast Stop” (H2-oo = 4C

<1>

) will be closed as long as Fast Stop is active.

<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.

No.

Parameter Name

Setting Range

Default

C1-09

Fast Stop Time

0.1 to 6000.0 s

10.0 s

NOTICE: Rapid deceleration can trigger an overvoltage fault. The drive output shuts off when faulted and the motor coasts. Set an

appropriate Fast Stop time to C1-09 to avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely.

u

C2: S-Curve Characteristics

Use S-curve characteristics to smooth acceleration and deceleration and minimize abrupt shock to the load. Set S-curve

characteristic time during acceleration/deceleration at start and acceleration/deceleration at stop.

n

C2-01 and C2-02: S-Curve Characteristics

C2-01 and C2-02 set separate S-curves for each section of the acceleration or deceleration.

No.

Parameter Name

Setting Range

Default

C2-01

S-Curve Characteristic at Accel Start

0.00 to 10.00 s

0.20 s

C2-02

S-Curve Characteristic at Accel End

0.20 s

Figure 5.15

illustrates S-curve application.

5.4 C: Tuning

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

139

5

Programming

Advertising