Setting 0: Disabled
The drive uses the frequency reference to determine the direction of motor rotation to restart the motor.
Setting 1: Enabled
The drive detects the motor rotation direction to restart the motor.
n
b3-17: Speed Search Restart Current Level
Sets the current level at which Speed Estimation is restarted as a percentage of drive rated current to avoid overcurrent and
overvoltage problems since a large current can flow into the drive if the difference between the estimated frequency and the
actual motor speed is too big when performing Speed Estimation.
No.
Name
Setting Range
Default
b3-17
Speed Search Restart Current Level
0 to 200%
110%
n
b3-18: Speed Search Restart Detection Time
Sets the time for which the current must be above the level set in b3-17 before restarting Speed Search.
No.
Name
Setting Range
Default
b3-18
Speed Search Restart Detection Time
0.00 to 1.00 s
0.10 s
n
b3-19: Number of Speed Search Restarts
Sets the number of times the drive should attempt to find the speed and restart the motor. If the number of restart attempts
exceeds the value set to b3-19, the SEr fault will occur and the drive will stop.
No.
Name
Setting Range
Default
b3-19
Number of Speed Search Restarts
0 to 10
3
n
b3-24: Speed Search Method Selection
Sets the Speed Search method.
No.
Parameter Name
Setting Range
Default
b3-24
Speed Search Method Selection
0, 1
0
Setting 0: Current Detection
Setting 1: Speed Estimation
Note:
Refer to Current Detection Speed Search (b3-24 = 0) on page 122
Refer to Speed Estimation Type Speed Search (b3-24 = 1) on
for explanations of the Speed Search methods.
n
b3-25: Speed Search Wait Time
Sets the wait time between Speed Search restarts. Increase the wait time if problems occur with overcurrent, overvoltage, or
if the SEr fault occurs.
No.
Name
Setting Range
Default
b3-25
Speed Search Wait Time
0.0 to 30.0 s
0.5 s
n
b3-27: Start Speed Search Select
Selects a condition to activate Speed Search Selection at Start (b3-01) or External Speed Search Command 1 or 2 from the
multi-function input.
No.
Name
Setting Range
Default
b3-27
Start Speed Search Select
0, 1
0
5.2 b: Application